Notes
Date Text
2005-09-14 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- ENERGY CALCS ARE GETTING THE CEILING
 FANS CREDIT. NEED TO SPECIFY CEILING
 SIZES IN THE ELECTRICAL PLAN, INCLUDING
 FANS REQUIRED IN THE GREAT ROOM. SEE
 TABLE 6-6 CHAPTER 13 FBC 2001.
  
 3- ROOF FRAMING PLAN NEEDS TO BE REVISED
 AT ENTRY PORCH AREA. CONCRETE BEAM
 DOESN'T EXTEND ALL THE WAY BACK TO THE
 FOYER AREA. ALSO, REVISE THE KNEEWALL AT
 THE LEFT HAND SIDE OF THE PORCH ROOF.
 IT'S NOT CONCRETE BEAM EITHER. SEE PLANS
 AND REVISE FRAMING PLAN AS REQUIRED AND
 SPECIFY CORRESPONDING CONNECTORS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
 4- TRUSS ANCHOR SCHEDULE. REVISE NUMBER
 OF NAILS FOR HUS26. SEE 2005 CATALOGUE.
  
 5- PROVIDE FLORIDA/LOCAL PRODUCT
 APPROVAL FOR:
 A) INSWING 1HR FIRE RATED DOOR AS SHOWN
 IN PLANS. SEE ATRIUM.
 B) WINDOW MULLION SPECIFIED FOR FIXED
 WINDOWS AT GREAT ROOM AREA.
 C) FIXED WINDOWS: NEED FLORIDA APPROVAL.
 D) SINGLE HUNG WINDOWS. NEED FL APPROVAL
 E) ROOF TILE. NEED FLORIDA APPROVAL.
  
 6- SPECIFY SIZE AND ANCHORS FOR WINDOW
 MULLION AT FIXED WINDOWS IN THE GREAT
 ROOM. MULLION SPECIFIED IN THE WINDOW
 SCHEDULE DON'T RESIST THE DESIGN
 PRESSURES. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.