Plan Review Notes
Plan Review Notes For Permit 05080587
Permit Number 05080587
Review Stop B
Sequence Number 1
Notes
Date Text
2005-09-13 00:00:00BUILDING REVIEW CHECKLIST:
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 2- ENERGY CALCS ARE GETTING THE CEILING
 FAN CREDIT. NEED TO SPECIFY CEILING
 SIZES IN THE ELECTRICAL PLAN, INCLUDING
 FANS REQUIRED AT GREAT ROOM. SEE TABLE
 6-6 CHAPTER 13 FBC 2001.
  
 3- ROOF FRAMING PLAN NEEDS TO BE REVISED
 AT ENTRY PORCH AREA TO MATCH FOUNDATION
 AND FLOOR PLAN. CONCRETE BEAM DOESN'T
 EXTEND ALL THE WAY BACK TO THE FOYER.
 CONCRETE BEAM IS ONLY AT ENTRY PORCH
 AREA. REVISE ROOF FRAMING PLAN AS
 REQUIRED AND SPECIFY CORRESPONDING
 CONNECTORS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 4- TRUSS ANCHOR SCHEDULE: REVISE NUMBER
 OF NAILS SPECIFIED FOR CONNECTOR HUS26.
 SEE 2005 CATALOGUE.
  
 5- ONE HR FIRE RATED DOOR AT ATRIUM
 PRODUCT APPROVAL SUBMITTED IS FOR
 OUTSWING DOOR. PLANS SHOW INSWING DOORS.
 REVISE AS REQUIRED.
  
 6- SPECIFY MULLION SIZE AND ANCHORS FOR
 FIXED WINDOWS AT GREAT ROOM. SIZE OF
 MULLION SPECIFIED ON WINDOW SCHEDULE
 DOESN'T RESIST THE CALCULATED DESIGN
 PRESSURES. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 7- PROVIDE PRODUCT APPROVAL FOR WINDOW
 MULLION SIZE AS SPECIFIED ABOVE.
  
 8- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL (FLORIDA APPROVAL WAS NOT
 SUBMITTED) FOR:
 A) ROOF TILE.
 B) SINGLE HUNG WINDOWS.
 C) FIXED WINDOWS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.