Plan Review Notes For Permit 05080522
Permit Number 05080522
Review Stop B
Sequence Number 2
Notes
Date Text
2005-09-28 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080522
 ADD: 8057 CRANES POINT WAY
 CONT: DANIEL ELECTRIC
 TEL: (561)848-9495
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 1) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
  
 2) SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BE USED.
 DISCREPANCY IN INFORMATION, PAGES
 FROM DANIEL ELECTRIC, AND INFORMATION ON
 SURVEY DO NOT MATCH THE GENERATOR SIZE,
 NO INFORMATION ON THE HOLD DOWN DEVICES
 OR SLAB SIZE.
  
 3) THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 4) PAGES SUBMITTED CORRELATE INTO (2)
 SETS OF PLANS.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  