2005-08-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)SEE ATTACHED POLICY.PLEASE
 INCLUDE MEAN ROOF HEIGHT AND DECK TYPE
 SO THAT CODE COMPLIANCE CAN BE
 DETERMINED.
  
 2.)THE APPLICATION STATES "TEAR OFF",
 THE SHEET SUBMITTED IS FOR RECOVER.A
 RECOVER IS GOING OVER AN EXISTING ROOF.
  
 3.)SUBMIT THE FIRST SHEETS OF THE NOA
 WHICH DESCRIBE THE COMPONENTS OF THE
 APPROVED ASSEMBLIES, THE ONE OR TWO
 SHEETS FOR THE APPROVED ASSEMBLY YOU ARE
 USING, AND THE LAST SHEET OR TWO OF THE
 NOA WHICH HAVE THE PRODUCT LIMITATIONS.
  
 4.)THE MAX DESIGN PRESSURE IS -52.5;
 NON COMPLIANT (NEEDS -89 OR HAVE PRODUCT
 LIMITATION #7 REFERRED TO IN THE
 APPROVED ASSEMBLY WHICH ALLOWS ENHANCED
 FASTENING).
  
 5.)THE STATE PRODUCT APPROVAL STATES
 "VALIDATED".PLEASE CHECK THE 2001
 FLORIDA BUILDING CODE DATABASE ON THE
 WEBSITE TO SEE IF THERE IS A CURRENT
 (APPROVED) STATE PRODUCT APPROVAL.CALL
 ME IF YOU NEED ASSISTANCE.