2005-08-09 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2001 |
| |
| 1.)SEE ATTACHED POLICY.PLEASE |
| INCLUDE MEAN ROOF HEIGHT AND DECK TYPE |
| SO THAT CODE COMPLIANCE CAN BE |
| DETERMINED. |
| |
| 2.)THE APPLICATION STATES "TEAR OFF", |
| THE SHEET SUBMITTED IS FOR RECOVER.A |
| RECOVER IS GOING OVER AN EXISTING ROOF. |
| |
| 3.)SUBMIT THE FIRST SHEETS OF THE NOA |
| WHICH DESCRIBE THE COMPONENTS OF THE |
| APPROVED ASSEMBLIES, THE ONE OR TWO |
| SHEETS FOR THE APPROVED ASSEMBLY YOU ARE |
| USING, AND THE LAST SHEET OR TWO OF THE |
| NOA WHICH HAVE THE PRODUCT LIMITATIONS. |
| |
| 4.)THE MAX DESIGN PRESSURE IS -52.5; |
| NON COMPLIANT (NEEDS -89 OR HAVE PRODUCT |
| LIMITATION #7 REFERRED TO IN THE |
| APPROVED ASSEMBLY WHICH ALLOWS ENHANCED |
| FASTENING). |
| |
| 5.)THE STATE PRODUCT APPROVAL STATES |
| "VALIDATED".PLEASE CHECK THE 2001 |
| FLORIDA BUILDING CODE DATABASE ON THE |
| WEBSITE TO SEE IF THERE IS A CURRENT |
| (APPROVED) STATE PRODUCT APPROVAL.CALL |
| ME IF YOU NEED ASSISTANCE. |