Plan Review Notes For Permit 05080349 |
Permit Number |
05080349 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-08-28 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05080349 | | ADD: 114 GOLF AVE | | CONT: SUNRISE ROOFING | | TEL: (561)963-9955 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 3RDREVIEW | | ACTION: DENIED | | 1) THIS ROOF IS MISSING OR NOT IN | | COMPLIANCE WITH THE FOLLOW ITEMS: | | | | ___ CONTRACTOR DID NOT PROVIDE THE MEAN | | | | ROOF HEIGHT. | | | | ___ CONTRACTOR DID NOT INDICATE THE ROOF | | PITCH. | | | | ___ CONTRACTOR FAILED TO INDICATE WHICH | | SYSTEM TO BE USED. | | | | _X__ THE SYSTEM PROVIDED HAS A LOW | | PRESSURE FOR ZONE3___ . | | MAXIMUM DESIGN PRESSURE: REFER TO | | TILE MANUFACTURER'S NOA> | | | | _X__ THE SYSTEM PROVIDED STATES | | LIMITATION# 7, SHOULD THE FASTENER | | RESISTANCE BE LESS THAN THAT | | REQUIRED, AS DETERMINED BY THE | | BUILDING OFFICIAL, A REVISED | | FASTENER SPACING, PREPARED , SIGNED | | | | AND SEALED BY A FLORIDA REGISTERED | | PROFESSIONAL ENGINEER, REGISTERED | | ARCHITECT OR REGISTERED ROOF | | CONSULTANT MAY BE SUBMITTED. | | | | ___THE SYSTEM PROVIDED INDICATES | | LIMITATION# 9, NO ENHANCED | | FASTENING ALLOWED. | | | | __X__ THE FLAT ROOF SYSTEM HIGHLIGHTED | | IS : SYSTEM TYPE E-2 RUBEROID TILE | | | | UNDERLAYMENT. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | |
|