2006-01-30 00:00:00 | DENIED |
| (2ND REVIEW) |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE STRUCTURE IS LOCATED IN AN "AO" |
| FLOOD ZONE. AN ELEVATION CERTIFICATE |
| WILL BE REQUIRED. |
| |
| 3) ADDITIONAL PERMIT FEES ARE DUE. THE |
| CALCULATED VALUE OF THE STRUCTURE IS |
| $1,001,140.00. A WESTWARD EXPANSION FEE |
| OF $550.00 PER UNIT IS ALSO REQUIRED. |
| |
| 4) SITE PLANS ARE REQUIRED WHICH |
| SPECIFY THE DISTANCE TO ASSUMED PROPERTY |
| LINES BETWEEN ADJACENT BUILDINGS LOCATED |
| ON THE SAME LOT. THIS IS REQUIRED IN |
| ORDER TO DETERMINE THE PERCENTAGE OF |
| WALL AREA THAT IS ALLOWED AS OPENINGS BY |
| FBC TABLE 600. |
| |
| 5) THE SCALE SPECIFIED IN THE INDEX ON |
| A1 FOR THE DRAWINGS ON SHEET A4 IS |
| INCORRECT. THE CORRECT SCALE IS 1/8". |
| |
| 6) THE CONSTRUCTION TYPE SPECIFIED ON A1 |
| IS FROM THE 2004 FBC. THESE PLANS WERE |
| REVIEWED UNDER THE 2001 FBC AND THE |
| STRUCTURAL PLANS ARE ON THE 2001 FBC. |
| PLEASE REVISE SHEETS A1 AND A9. |
| |
| 7) BASED ON TYPE VI CONSTRUCTION, |
| UNPROTECTED AND UNSPRINKLERED, 2001 FBC |
| TABLE 500 LIMITS THE AREA PER FLOOR TO |
| 7000 SQFT. USING THE FORMULA FOR AREA |
| INCREASES ALLOWED BY SECTION 503.3, AND |
| THE FRONT AND REAR BUILDING PERIMETERS |
| WHICH 30FT WIDE HORIZONTAL SEPARATIONS |
| THE ALLOWABLE AREAS ARE EXCEEDED AT THE |
| SECOND FLOOR. IF THE PORTIONS OF THE |
| LEFT AND RIGHT SIDE PERIMETERS THAT HAVE |
| 30FT TO THE ASSUMED PROPERTY LINE |
| BETWEEN BUILDINGS (SEE SECTION 505) WERE |
| USED IN THE CALCULATIONS THE AREA |
| INCREASE ALLOWED MAY COMPLY. HOWEVER, NO |
| SITE PLAN INDICATING ASSUMED PROPERTY |
| LINES WAS SUBMITTED. SUBMIT AREA |
| INCREASE CALCULATIONS. |
| |
| 8)CONDOMINIUM V APARTMENTS.IF THE |
| DWELLING UNITS ARE TO BE SOLD AS |
| CONDOMINIUMS, A 'DECLARATION OF |
| CONDOMINIUM' SHALL BE SUBMITTED TO THE |
| STATE FOR APPROVAL, AND THEN RECORDED |
| WITH THE CLERK OF THE COUNTY COURT.A |
| RECORDED COPY SHALL BE SUBMITTED TO THE |
| CITY FOR RECORDS, ADDRESSING PURPOSES, |
| AND TO PALM BEACH COUNTY PROPERTY |
| APPRAISER'S OFFICE PRIOR TO C.O. |
| |
| 9) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 10) ON SHEET S5 UNDER PLYWOOD ROOF |
| DIAPHRAGM, NOTE #3 SPECIFIES 8D GAL. |
| NAILS AT 6"OC AT EDGES AND INTERMEDIATE. |
| THIS CONFLICTS WITH ROOF PLAN ON S4, |
| WHICH SPECS. 10D NAILS 4"OC AT EDGES AND |
| 6"OC INTERMEDIATE. THE CITY AMENDMENTS |
| TO FBC TABLE 2306.1 REQUIRE 8D |
| RING-SHANK NAILS 4"OC AT EDGES AND 6"OC |
| INTERMEDIATE IN ZONE 3 FOR ROOFS WITH A |
| MEAN ROOF HEIGHT OF MORE THAN 25'. |
| |
| 11) PLEASE REVISE THE STANDARDS |
| REFERENCED UNDER DESIGN CRITERIA ON S5 |
| TO THE EDITIONS LISTED IN CHAPTER 35 OF |
| THE 2001 FBC. (ACI 318-02 AND 530.1-02) |
| |
| 12) SPECIFY METHOD OF TERMITE PROTECTION |
| AS REQUIRED BY FBC 1816. |
| |
| 13) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE |
| AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| BE SUBMITTED WITH A COVER SHEET THAT |
| LISTS THE PRODUCT IDENTITY NUMBER FROM |
| THE STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. |
| |
| 14) SPECIFY HOW IMPACT PROTECTION WILL |
| BE PROVIDED FOR THE GLAZED OPENINGS AS |
| REQUIRED BY FBC 1606.1.4. ITEM #13 OF |
| THE CITY OF WPB IMPLEMENTATION STANDARD |
| FOR HURRICANE MISSLE IMPACT PROTECTION |
| REQUIRES PRE-STORM PREPARATION PLANS TO |
| BE SUBMITTED FOR REVIEW IF USING STORM |
| SHUTTERS, IN ADDITION TO A KEY PLAN, |
| INSTALLATION SCHEDULE AND PRODUCT |
| APPROVALS. STORM PANELS ARE NOT ALLOWED |
| ABOVE THE FIRST FLOOR FOR THIS TYPE OF |
| STRUCTURE AND OCCUPANCY. |
| |
| 15) SUBMIT THE EVALUATION REPORT AND |
| INSTALLATION INSTRUCTIONS FROM NATIONAL |
| ACCREDITATION AND MANAGEMENT INSTITUTE |
| FOR THE THERMA-TRU DOORS WITH FL # 1170. |
| THE INFORMATION THAT WAS SUBMITTED TO |
| THE STATE FOR STATE PRODUCT APPROVAL IS |
| REQUIRED TO BE SUBMITTED WITH THE STATE |
| COVER SHEET. |
| |
| 16) SUBMIT PRODUCT APPROVAL FOR THE |
| SMALL (8' X 7') OVERHEAD GARAGE DOOR |
| WHICH IS LESS THAN THE MINIMUM SIZE |
| ALLOWED BY THE PRODUCT APPROVAL FOR THE |
| LARGE DOOR THAT WAS SUBMITTED. |
| |
| 17) SUBMIT THE SBCCI REPORT (2139A) THAT |
| IS LISTED ON THE FL PRODUCT APPROVAL |
| WEBSITE FOR THE COLLIER GARAGE DOORS. |
| |
| 18) SUBMIT PRODUCT APPROVALS FOR THE |
| TRUSS CONNECTORS. |
| |
| 19) PROVIDE A STRUCTURAL DETAIL ON THE |
| PLANS FOR THE CONCRETE STAIRS. SPECIFY |
| STEEL REINFORCEMENT FOR THE STAIRS, |
| LANDINGS AND AT THE BASE OF THE STAIRS. |
| |
| 20) SUBMIT SIGNED AND SEALED TRUSS |
| DRAWINGS AND LAYOUTS THAT HAVE REVIEWED |
| AND APPROVED BY THE DESIGNER OF RECORD |
| FOR THE STRUCTURE. |
| |
| 21) SUBMIT A TECHNICAL BULLETIN OR |
| REPORT FROM USP THAT ALLOWS TRUSS HANGER |
| JUS26-2 TO BE ATTACHED TO MASONRY WITH |
| TAPCON FASTENERS AND SPECIFYING THE |
| ALLOWABLE LOADS FOR THE APPLICATION. |
| |
| 22) PROVIDE SHOP DRAWINGS WITH |
| STRUCTURAL DETAILS FOR THE TYPICAL |
| INTERIOR GUARDRAIL DETAIL AS |
| REFERENCED BY THE SECTION ON A12. |
| |
| 23) SUBMIT SHOP DRAWINGS FOR THE |
| EXTERIOR GUARDRAILS. INDICATING HOW THEY |
| WILL BE ATTACHED TO THE STRUCTURE. |
| |
| 24) THE ENGINEER IS REQUIRED TO SIGN HIS |
| NAME TO THE PLANS HE SEALS PER FAC |
| 61G15-23.002. PLEASE SUBMIT A NOTARIZED |
| LETTER SIGNED, SEALED AND DATED BY THE |
| ENGINEER ATTESTING HIS LEGAL SIGNATURE. |
| |
| 25) THE 5' BI-PASS DOOR AT HER WALK-IN |
| CLOSET (#7 IN SCHEDULE) DOES NOT COMPLY |
| WITH FAIR HOUSING REQUIREMENTS. USEABLE |
| DOORS WITHIN THE DWELLING UNIT MUST HAVE |
| A CLEAR OPENING OF AT LEAST 31-5/8" |
| CLEAR. |
| |
| 26) THE STRUCTURAL PLANS DO NOT SHOW THE |
| ELEVATOR RECESSES ON THE FOUNDATION PLAN |
| OR THE OPENINGS AT THE SECOND FLOOR FOR |
| THE ELEVATORS. PROVIDE STRUCTURAL |
| DETAILS FOR THESE AREAS. |
| |
| 27) PROVIDE STRUCTURAL DETAILS FOR THE |
| INFILL FLOOR FRAMING AT THE ELEVATOR |
| RECESSES AND OPENINGS WHEN THE CLOSET |
| OPTION IS USED IN LEIU OF AN ELEVATOR. |
| SEE DETAILS 6 AND 7 ON A11. |
| |
| 28) THE 16' GARAGE DOORS ON SHEETS A8GR |
| AND A8GL HAVE THE WRONG ID MARKS |
| ACCORDING TO THE DOOR SCHEDULE ON A9. |
| |
| 29) THE 8' WIDE GARAGE DOOR ON A8GL-C |
| HAS THE WRONG ID MARK PER THE DOOR |
| SCHEDULE. |
| |
| 30) ON A6GR-C THE DOOR ID MARKS DO NOT |
| CORRESPOND WITH THE DOOR SCHEDULE ON A9. |
| |
| 31) THE WALL SECTION ON A13 STATES THAT |
| METAL LATH SHALL COMPLY WITH SECTIONS |
| 2507.3 THRU 2507.5. THESE SECTIONS ARE |
| FROM THE HIGH VELOCITY HURRICANE ZONE |
| (DADE & BROWARD COUNTIES) AND APPLY TO |
| GYPSUM LATH. PLEASE CORRECT. |
| |
| 32) ORIGINAL APPLICATION, SURVEYS, |
| IMPACT FEE RECEIPT AND PRODUCT APPROVALS |
| ARE MISSING. |
| |