Plan Review Notes
Plan Review Notes For Permit 05080279
Permit Number 05080279
Review Stop P
Sequence Number 1
Notes
Date Text
2005-09-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 1. ALL FIRST FLOOR UNITS SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FAIR
 HOUSING ACT DESIGN MANUAL. PLEASE SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH ALL
 REQUIREMENTS. INDICATE SPECIFICATION "A"
 OR "B" AS REQUIRED ON PAGE 7.34. THE
 CLEAR FLOOR SPACE FOR ALL USABLE
 FIXTURES SHALL BE APPLIED OR
 SUPERIMPOSED OVER THE FLOOR PLAN. FOR
 THE W/C SEE PAGE 7.43.
 2. SHTS P1 OF 2 FOR UNITS 101, 102, 103,
 201,202, & 203 MAXIMUM 6 FT. FROM SHOWER
 TRAP TO VENT PER TABLE 906.1. ON THE
 FLOOR PLAN IT SCALES OUT TO APPROX. 8'
 TO 9'.
 3. SHTS P2 OF 2 FOR UNITS 101, 102, 103,
 201, 202, & 203 WATER RISER DIAGRAM.
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SOME ARE SHOWN.
 PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS.
 4. SHTS P2 OF 2 ALL UNITS WATER HEATER
 DETAIL. P/T DISCHARGE LINE SHALL NOT
 HAVE ANY TRAPED SECTIONS. SECTION
 504.7.1. (SEE WATER HEATER NOTES).
 5. SHTS P2 OF 2 ALL UNITS SANITARY RISER
 DIAGRAM. THE WASH MACHINES DRAIN LINE
 SHALL HAVE A STANDPIPE, SECTION 1002.1.,
 AND THE CLEANOUT SHALL BE LOCATED 4'
 ABOVE THE FLOOR, SECTION 708.10 FOR
 ACCESS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]