2005-09-28 00:00:00******DENIED******
  
 1) ADDRESS IS REQUIRED ON EACH BUILDING.
 IT SHALL BE A MINIMUM OF 3" AND
 CONTRASTING TO THE BACKGROUND.
  
 2) PLEASE PROVIDE PRESCRIPTIVE STRENGTH
 REQUIREMENTS FOR ALL HANDRAILS AND
 GUARDS.
  
 3) ARE THESE BUILDINGS FIRE SPRINKLERED?
  
  
 4) FIRE HYDRANTS SHALL BE WET BEFORE,
 DURING AND AFTER CONSTRUCTION.
  
 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED FOR EACH UNIT.
  
 6) ELEVATORS SHALL COMPLY WITH A.S.M.E
 A-17.1.
  
 7) PLEASE USE THE 2003 EDITION WHEN
 REFERENCING NFPA 101. SHT 4-A9.
  
 8) SMOKE DETECTORS SHALL BE ARRANGED
 WHERE ACTIVATION OF ONE CAUSES ALL IN
 THE UNIT TO SOUND.
  
 9) ALL CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 10) STAIRS TO COMPLY WITH NFPA 101,
 SECTION 7.2.2.
  
 11) SMOKE DETECTORS TO BE INSTALLED A
 MINIMUM OF 3' FROM HVAC DIFFUSERS.
  
 12) PLEASE SEE SOME OF THE SMOKE
 DETECTORS NEAR #2 BEDROOMS APPEAR TO
 CLOSE TO THE BATHROOM.
  
 13) HANDRAILS REQUIRED ON BOTH SIDES OF
 STAIRS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722