2005-08-26 00:00:00 | ***********UNSAT ************ |
| |
| BLDG #5. |
| |
| |
| 1)NOTE: PLEASE CHECK AND VERIFY ALL SETS |
| AND CORRECT SHEETS IN ORDER. |
| |
| 2)NOTE: PLEASE SEE APPLICATION SHOWS |
| THESE BEING SUBMITTED AS "TOWNHOUSES"?? |
| PLEASE SEE BUILDING REVIEW COMMENTS. |
| THESE DO NOT SEEM TO BE CONSIDERED TRUE |
| "TOWNHOUSES" AS DEFINED UNDER THE FBC. |
| PLEASE SEE PALM BEACH COUNTY IMPACT FEE |
| STAMPED INDICATES BUILDINGS AS 4 AND 6 |
| UNIT MULTI FAMILY DWELLINGS. |
| |
| PLEASE SEE THE FOLLOWING COMMENT FOR |
| ELECTRICAL SERVICE. |
| |
| 3)NOTE: PLEASE SEE DUE TO THESE NOT |
| BEING CONSIDERED AS TOWNHOUSES WITH |
| SEPARATE PROPERTY LINES, FEE SIMPLE ETC. |
| ONLY ONE ELECTRICAL SERVICE WILL BE |
| PERMITTED. PLEASE SEE GROUPING OF MAINS |
| WILL BE REQUIRED FOR ALL FOUR UNITS IN |
| THIS BLDG UNDER ONE SERVICE. |
| PLEASE ADJUST SIZE OF SERVICE |
| ACCORDINGLY. (SEC'S, GROUNDING, |
| CONDUITS, ETC. |
| 230.2,230.70,230.72,240.4,310.16 |
| |
| 4)NOTE: PLEASE SEE MISSING AREAS FOR |
| EGRESS LIGHTING. PLEASE SEE SOME AREAS |
| WHERE AS "J-BOX" IS SHOWN, A LT FIXTURE |
| OFSOME TYPE WILL BE REQUIRED. PLEASE |
| SEE ENTRIES, TERRACE(1ST FLR) LIV RMS, |
| KITCHENS ETC. |
| PLEASE SEE 2-STORY UNITS, A 3-WAY OR |
| 4-WAY SWITCH WILL BE REQUIRED AT THE |
| LANDINGS LOCATED IN BETWEEN FLRS. |
| THIS IS ALSO REQUIRED FROM 210.70,LS 101 |
| 5-8 |
| |
| 5)NOTE: PLEASE SEE MISSING SMOKE |
| DETECTORS FOR AREAS LEADING TO FLR |
| ABOVE. PLEASE SEE ENTRY FOYER'S FOR |
| 2-STORY UNITS. NFPA-72 8-1.4.1.6.2 |
| PLEASE ALSO SEE SD'S FOR MASTER BEDRM |
| SHALL BE MOED "INTO" BEDRM AREA. PLEASE |
| SEE ALL SD'S ARE TO BE INSTALLED WITHIN |
| 3' OF THE PEAK IN A SLOPE CEILING AND IN |
| TRAY/ELEVATED CEILINGS WITHIN 12" OF MAX |
| CEILING HEIGHT. |
| NFPA-72 CHAPTER 2. |
| PLEASE SEE SD'S ARE TO BE LOCATED NO |
| CLOSER THAN 3' TO ANY KITCHEN OR BATH |
| DOOR. AND 5' TO A RETURN AIR GRILL. |
| NFAP-72 8-1.4.2 |
| PLEASE SEE SOME OF THESE HAVE BEEN |
| REDLINED ON ONE SET OF PLANS. |
| |
| 6)NOTE: PLEASE SEE SD'S ARE CIRCUITED TO |
| KITCHEN/DINING LTS. THIS IS OK, HOWEVER |
| PLEASE KNOW, THIS CIRCUIT WOULD BE ARC |
| FAULT PROTECTED. PLEASE SEE THIS MEANS |
| KITCHEN AND DINING RM LTS AS SHOWN WOULD |
| BE INDICATED AS AFCI. |
| PLEASE SEE SD'S MAY BE ON AN EXISITNG |
| BEDRM ARC FAULT PROTECTED CIRCUIT. |
| 210.12, 2002 NEC. |
| |
| 7)NOTE: PLEASE VERIFY OF GFI SHOWN IN |
| KITCHEN IS "IN" THE PANTRY? PLEASE SEE |
| KITCHENS WHEREPANTRY IS NOT SHOWN, AND |
| A COUNTERSPACE IS ALSO NOT INDICATED?? |
| |
| 8)NOTE: PLEASE SEE MISSING GFI RECEPTS |
| AND LTS FOR ELEVATOR PITAND EQUIPMENT |
| SPACE. EACH SHALL CONTAIN DEDICATED |
| CIRCUITS PER 620.23,620.24 |
| |
| |
| PLEASE SEE MANY OF THE ABOVE ITEMS WERE |
| REDLINED ON PLANS FOR AREAS OF NOTES. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REVIEWERS, WHICH MAY AFFECT |
| ELECTRICAL PLANS. (BLDG). |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |