2005-09-22 00:00:00 | DENIED |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE STRUCTURE IS LOCATED IN AN "AO" |
| FLOOD ZONE. AN ELEVATION CERTIFICATE |
| WILL BE REQUIRED. |
| |
| 3) ADDITIONAL PERMIT FEES ARE DUE. THE |
| CALCULATED VALUE OF THE STRUCTURE IS |
| $1,001,140.00. A WESTWARD EXPANSION FEE |
| OF $550.00 PER UNIT IS ALSO REQUIRED. |
| |
| 4) SITE PLANS ARE REQUIRED WHICH |
| SPECIFY THE DISTANCE TO ASSUMED PROPERTY |
| LINES BETWEEN ADJACENT BUILDINGS LOCATED |
| ON THE SAME LOT. THIS IS REQUIRED IN |
| ORDER TO DETERMINE THE PERCENTAGE OF |
| WALL AREA THAT IS ALLOWED AS OPENINGS BY |
| FBC TABLE 600. |
| |
| 5) THESE UNITS DO NOT MEET THE |
| DEFINITION OF TOWNHOUSE IN THE 2001 |
| FLORIDA BUILDING CODE. PLEASE REMOVE THE |
| TITLE OF TOWNHOMES FROM THE TITLE BLOCKS |
| OF THE M.E.P. DRAWINGS. |
| |
| 6) SPECIFY THE SCALE OF THE DRAWINGS ON |
| THE PLANS. |
| |
| 7) SPECIFY THE OCCUPANCY, CONSTRUCTION |
| TYPE, PROTECTED OR UNPROTECTED AND |
| SPRINKLERED OR UNSPRINKLERED. PROVIDE |
| ARES INCREASE CALCULATIONS. |
| |
| 8)CONDOMINIUM V APARTMENTS.IF THE |
| DWELLING UNITS ARE TO BE SOLD AS |
| CONDOMINIUMS, A 'DECLARATION OF |
| CONDOMINIUM' SHALL BE SUBMITTED TO THE |
| STATE FOR APPROVAL, AND THEN RECORDED |
| WITH THE CLERK OF THE COUNTY COURT.A |
| RECORDED COPY SHALL BE SUBMITTED TO THE |
| CITY FOR RECORDS, ADDRESSING PURPOSES, |
| AND TO PALM BEACH COUNTY PROPERTY |
| APPRAISER'S OFFICE PRIOR TO C.O. |
| |
| 9) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 10) FBC 705.1.3.2.1 CLASSIFIES FIRE |
| DOORS AS 3 HOUR, 1-2/2 HOUR, 1 HOUR, 3/4 |
| HOUR OR 20 MINUTE. REVISE THE 'C' LABEL |
| DOOR SPECIFIED ON SHEET A9. FBC |
| 705.1.3.2.2 ALLOWS 20 MINUTE RATED DOORS |
| IN WALLS REQUIRED TO HAVE A FIRE |
| RESISTANCE RATING OF 1 HOUR OR LESS. |
| |
| 11) FBC 705.1.3.5 REQUIRES FIRE DOORS TO |
| BE EQUIPED WITH AN APPROVED CLOSER. |
| |
| 12) PROVIDE A ROOF SHEATHING NAILING |
| PLAN FOR THE LOWER ROOFS THAT ARE NOT |
| SHOWN ON S4. |
| |
| 13) THE SPACING OF THE TAPCON FASTENERS |
| FOR THE GARAGE DOOR HEADER IN DETAIL 1 |
| ON S4 APPEAR TO CONFLICT. 16"OC IS |
| SPECIFIED IN ONE PLACE AND 8" OC IS |
| SPECIFIED UNDER NOTES. PLEASE CORRECT. |
| |
| 14) FBC TABLE 1604.1 REQUIRES THE BOTTOM |
| CORD LIVE LOAD TO BE 10 PSF FOR ATTICS |
| WITHOUT STORAGE AND 30 PSF FOR ATTICS |
| WITH STORAGE. REVISE ROOF LOADS ON S5. |
| |
| 15) UNDER GENERAL NOTES ON S5, ITEM # 24 |
| SPECIFIES THE WRONG EDITIONS OF ACI, |
| ASCE 5 AND TMS. THE 2002 EDITIONS ARE |
| REFERENCED IN CHAPTER 35 OF THE 2001 FBC |
| |
| 16) UNDER STRUCTURAL DESIGN CRITERIA ON |
| S5, THE CORRECT EDITIONS OF THE |
| REFERENCE STANDARDS ARE ACI 318-02 AND |
| ACI 5301-02. |
| |
| 17) THE EXTERIOR WALL SECTION 5 ON S6 |
| SPECIFIES 6" FROM THE TOP OF THE |
| MONOLITHIC SLAB TO FINISH GRADE. THIS |
| WILL NOT ALLOW THE BOTTOM OF THE 16" |
| DEEP FOOTER TO BE A MINIMUM 12" BELOW |
| FINISH GRADE AS REQUIRED BY FBC 1804.1.3 |
| |
| 18) THE ROOF PITCH ON THE WALL SECTION 5 |
| ON S6 AND THE TYPICAL ROOF TRUSS ANCHOR |
| DETAIL ON S3 ARE SPECIFIED AS 5/12 AND |
| THE ELEVATIONS SPECIFY 4/12. |
| |
| 19) THE UL SYSTEM SPECIFIED FOR THE ONE |
| HOUR FIRE RATED TENANT SEPARATION WALLS |
| "U 907" IS FOR NONBEARING WALLS ONLY. |
| PLEASE SPECIFY A SYSTEM FOR BEARING |
| WALLS. |
| |
| 20) THE LABELING OF THE UNITS AS TO |
| GARAGE LEFT OR RIGHT IS INCONSISTANT. TO |
| AVOID CONFUSION IF THE GARAGE IS LOCATED |
| TO THE LEFT OF ITS UNIT LABEL IT GARAGE |
| LEFT AND VISE VERSA FOR GARAGE RIGHT. |
| |
| 21) PROVIDE A DETAIL OF THE GUARDRAILS |
| AT THE OPEN SIDE OF THE STAIRS (LOWER |
| SECTION). SEE FBC 1015. |
| |
| 22) PROVIDE AN AREA TABULATION TABLE |
| LISTING THE FIRST AND SECOND FLOOR A/C |
| AREAS AND UNCONDITIONED AREAS FOR EACH |
| UNIT AND THE TOTALS FOR THE STRUCTURE. |
| |
| 23) THE ELEVATORS ARE REQUIRED TO COMPLY |
| WITH ASME A17.1 AND ANSI A117.1 (FAIR |
| HOUSING). |
| |
| 24) SPECIFY METHOD OF TERMITE PROTECTION |
| AS REQUIRED BY FBC 1816. |
| |
| 25) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE |
| AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| BE SUBMITTED WITH A COVER SHEET THAT |
| LISTS THE PRODUCT IDENTITY NUMBER FROM |
| THE STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 26) SPECIFY HOW IMPACT PROTECTION WILL |
| BE PROVIDED FOR THE GLAZED OPENINGS AS |
| REQUIRED BY FBC 1606.1.4. ITEM #13 OF |
| THE CITY OF WPB IMPLEMENTATION STANDARD |
| FOR HURRICANE MISSLE IMPACT PROTECTION |
| REQUIRES PRE-STORM PREPARATION PLANS TO |
| BE SUBMITTED FOR REVIEW IF USING STORM |
| SHUTTERS, IN ADDITION TO A KEY PLAN, |
| INSTALLATION SCHEDULE AND PRODUCT |
| APPROVALS. STORM PANELS ARE NOT ALLOWED |
| ABOVE THE FIRST FLOOR FOR THIS TYPE OF |
| STRUCTURE AND OCCUPANCY. |
| |
| 27) SUBMIT THE EVALUATION REPORT AND |
| INSTALLATION INSTRUCTIONS FROM NATIONAL |
| ACCREDITATION ANS MANAGEMENT INSTITUTE |
| FOR THE THERMA-TRU DOORS WITH FL # 1170. |
| THE INFORMATION THAT WAS SUBMITTED TO |
| THE STATE FOR STATE PRODUCT APPROVAL IS |
| REQUIRED TO BE SUBMITTED WITH THE STATE |
| COVER SHEET. |
| |
| 28) SUBMIT PRODUCT APPROVAL FOR THE |
| SMALL (8' X 7') OVERHEAD GARAGE DOOR |
| WHICH IS LESS THAN THE MINIMUM SIZE |
| ALLOWED BY THE PRODUCT APPROVAL FOR THE |
| LARGE DOOR THAT WAS SUBMITTED. |
| |
| 29) SUBMIT THE SBCCI REPORT (2139A) THAT |
| IS LISTED ON THE FL PRODUCT APPROVAL |
| WEBSITE FOR THE COLLIER GARAGE DOORS. |
| |
| 30) SUBMIT PRODUCT APPROVALS FOR THE |
| TRUSS CONNECTORS. |
| |
| 31) PROVIDE A STRUCTURAL DETAIL ON THE |
| PLANS FOR THE CONCRETE STAIRS. SPECIFY |
| STEEL REINFORCEMENT FOR THE STAIRS, |
| LANDINGS AND AT THE BASE OF THE STAIRS. |
| |
| 32) SUBMIT SIGNED AND SEALED TRUSS |
| DRAWINGS AND LAYOUTS THAT HAVE REVIEWED |
| AND APPROVED BY THE DESIGNER OF RECORD |
| FOR THE STRUCTURE. |
| |
| 33) SUBMIT A TECHNICAL BULLETIN OR |
| REPORT FROM USP THAT ALLOWS TRUSS HANGER |
| JUS26-2 TO BE ATTACHED TO MASONRY WITH |
| TAPCON FASTENERS AND SPECIFYING THE |
| ALLOWABLE LOADS FOR THE APPLICATION. |
| |
| 34) PROVIDE STRUCTURAL DETAILS FOR THE |
| TYPICAL INTERIOR GUARDRAIL DETAIL AS |
| REFERENCED BY THE SECTION ON A12. |
| |
| 35) SUBMIT SHOP DRAWINGS FOR THE |
| EXTERIOR GUARDRAILS. INDICATING HOW THEY |
| WILL BE ATTACHED TO THE STRUCTURE. |
| |
| 36) THE ENGINEER'S FIRM # IS REQUIRED TO |
| BE LISTED IN THE TITLE BLOCK. SEE FAC |
| 61G15-23.002. |
| |
| 37) THE ENGINEER IS REQUIRED TO SIGN HIS |
| NAME TO THE PLANS HE SEALS PER FAC |
| 61G15-23.002. PLEASE SUBMIT A NOTARIZED |
| LETTER SIGNED, SEALED AND DATED BY THE |
| ENGINEER ATTESTING HIS LEGAL SIGNATURE. |
| |
| 38) THE ARCHITECT IS REQUIRED TO |
| PERSONALLY SIGN ALL DOCUMENTS SEALED BY |
| HIM PER FAC 61G1-16.003. PLEASE SUBMIT A |
| NOTARIZED LETTER SIGNED, SEALED AND |
| DATED BY THE ARCHITECT ATTESTING HIS |
| LEGAL SIGNATURE. |
| |
| 39) SHOW COMPLIANCE WITH THE FAIR |
| HOUSING ACT. ALL BUILDING ENTRANCES ARE |
| REQUIRED TO BE ACCESSIBLE AND BE ON AN |
| ACCESSIBLE ROUTE. |
| - THE PRIMARY ENTRANCE DOOR MUST MEET |
| THE REQUIREMENTS FOR ACCESSIBLE DOORS |
| (32" CLEAR OPENING, LOW OR NO THRESHOLD- |
| 3/4"MAX, HARDWARE COMPLYING WITH ANSI |
| 4.13.9, ETC.) |
| - DOORS WITHIN UNITS MUST BE USEABLE |
| DOORS. MUST PROVIDE AT LEAST A 31-5/8" |
| CLEAR OPENING. |
| - CLOSET DOORS THAT REQUIRE USERS TO |
| PASS THROUGH THE DOORWAY TO REACH THE |
| CONTENTS MUST HAVE DOORS THAT PROVIDE AT |
| LEAST 32 INCHES NOMINAL CLEAR OPENING. |
| - LIGHT SWITCHES, ELECTRICAL OUTLETS, |
| THERMOSTATS AND CONTROLS SHALL BE IN |
| ACCESSIBLE LOCATIONS. |
| - INDICATE THE MINIMUM CLEAR FLOOR |
| SPACES AT THE FIXTURES AND APPLIANCES IN |
| THE KITCHENS. |
| - THE FAIR HOUSING ACT REQUIRES THE |
| BATHROOMS TO BE DESIGNED TO COMPLY WITH |
| SPECIFICATION "A" OR "B" BATHROOMS. |
| INDICATE WHICH ONE WILL BE USED AND SHOW |
| COMPLIANCE WITH DESIGN METHOD SELECTED. |
| ALL FIRST FLOOR UNITS AND ALL SECOND |
| FLOOR UNITS EQUIPPED WITH ELEVATORS ARE |
| REQUIRED TO COMPLY WITH THE FAIR HOUSING |
| REQUIREMENTS. |
| |
| 40) THE STRUCTURAL PLANS DO NOT SHOW THE |
| ELEVATOR RECESSES ON THE FOUNDATION PLAN |
| OR THE OPENINGS AT THE SECOND FLOOR FOR |
| THE ELEVATORS. PROVIDE STRUCTURAL |
| DETAILS FOR THESE AREAS. |
| |
| 41) PROVIDE STRUCTURAL DETAILS FOR THE |
| INFILL FLOOR FRAMING AT THE ELEVATOR |
| RECESSES AND OPENINGS WHEN THE CLOSET |
| OPTION IS USED IN LEIU OF AN ELEVATOR. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |
| |
| |