Plan Review Notes
Plan Review Notes For Permit 05080275
Permit Number 05080275
Review Stop M
Sequence Number 1
Notes
Date Text
2005-09-14 00:00:00PLAN DENIED
 101,102,103
 1) GARAGE EXHAUST MUST BE 10FT.FROM
 WINDOWS AND FRESH AIR INTAKE.SECTION
 401.5.1 AND 501.3 FBC(M) 2001.
 2) PLEASE REFER TO SECTION 504.6 CLOTHES
 DRYER DUCT.DUCT LENGTH LONGER THAN 25FT.
 3) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR.TRANSFER DUCT IN
 MASTER BEDROOM IS TO SMALL.FBC(M) 2001
 4)PLEASE REFER TO SECTION 301.14 FLOOD
 RAZARD.
 201,203
 1)PLEASE REFER TO SECTION 601.4
 EXCEPTION 3 TRANSFER DUCT IS NOT
 REQUIRED IN UTILITY ROOM.FBC(M)2001
 2) PLEASE REFER TO SECTION 301.14 FLOOD
 HAZARD FBC(M)2001
 3) NEED FAN SHUT DOWN SECTION 606.2.1
 SUPPLY AIR SYSTEM.FBC(M) 2001
 202
 1) PLEASE REFER TO SECTION 301.14 FLOOD
 HAZARD FBC(M) 2001
 2) PLEASE REFER TO SECTION 601.4
 EXCEPTION 3. BALANCED RETURN AIR
 AIR.TRANSFER DUCT IS NO REQUIRED IN
 UTILITY ROOM.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732