Plan Review Notes For Permit 05080175 |
Permit Number |
05080175 |
|
Review Stop |
E |
Sequence Number |
9 |
|
Notes |
Date |
Text |
2006-10-17 14:59:06 | CONTRACTOR CALLED, | | REMOVED OLD E-2, AS THIS RISER DOES NOT APPLY. | | | | RISERGROUNDING ELECTRODE CONDUCTOR NEEDS TO BE SIZED | | PER 250.66. THIS APPEARS IT SHOULD BE 2/0. |
|