Plan Review Notes
Plan Review Notes For Permit 05080175
Permit Number 05080175
Review Stop E
Sequence Number 7
Notes
Date Text
2006-09-05 00:00:00****UNSAT *****
  
 1) NOTE: PLEASE SEE PLANS NEED TO BE
 RE-PRINTED AS HAND DRAWN ITEMS ON PLANS
 ARE NOT PERMITTED.
 FBC ADMIN SECT 106.1.2
  
 2) NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR TO BE SIZED PER 250.66.
 PLEASE SEE SYSTEM SHALL BE CONTINUOUS.
 250.50,250.64.250.66
 1/0 MIN, #4 SHOWN.
 PLEASE ALSO VERIFY THE ATTCHMENT
 LOCATION OF THE GEC. SHOWN TO MAIN, IS
 THIS GOING TO THE GUTTER/, IF SO, PLEASE
 REVISE.
  
 3) NOTE: PLEASE KNOW, NEW REVISED PLANS
 DONE BY THE ENGINEER SHALL CONTAIN TITLE
 BLOCKS AS REQUIRED PER FAC 61G15-23.002,
 FS 471.023
  
 PLEASE REVISE THE ABOVE AND SUBMIT FOR
 REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  