Plan Review Notes For Permit 05080175 |
Permit Number |
05080175 |
|
Review Stop |
E |
Sequence Number |
7 |
|
Notes |
Date |
Text |
2006-09-05 00:00:00 | ****UNSAT ***** | | | | 1) NOTE: PLEASE SEE PLANS NEED TO BE | | RE-PRINTED AS HAND DRAWN ITEMS ON PLANS | | ARE NOT PERMITTED. | | FBC ADMIN SECT 106.1.2 | | | | 2) NOTE: PLEASE SEE GROUNDING ELECTRODE | | CONDUCTOR TO BE SIZED PER 250.66. | | PLEASE SEE SYSTEM SHALL BE CONTINUOUS. | | 250.50,250.64.250.66 | | 1/0 MIN, #4 SHOWN. | | PLEASE ALSO VERIFY THE ATTCHMENT | | LOCATION OF THE GEC. SHOWN TO MAIN, IS | | THIS GOING TO THE GUTTER/, IF SO, PLEASE | | REVISE. | | | | 3) NOTE: PLEASE KNOW, NEW REVISED PLANS | | DONE BY THE ENGINEER SHALL CONTAIN TITLE | | BLOCKS AS REQUIRED PER FAC 61G15-23.002, | | FS 471.023 | | | | PLEASE REVISE THE ABOVE AND SUBMIT FOR | | REVIEW. | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | |
|