Date |
Text |
2006-06-03 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| MUNICIPAL CODE |
| |
| 1. SUBMIT A SANITARY RISER DIAGRAM AND |
| PLAN VIEW OF THE PIPING. SHOW ALL PIPE |
| SIZES, VENTS, TRAPS ETC. SECTION |
| 104.3.1.1. |
| |
| 2. SUBMIT A WATER RISER DIAGRAM AND PLAN |
| VIEW OF THE PIPING. SHOW ALL PIPE SIZES, |
| VALVES AND WATER HAMMER ARRESTORS IF |
| REQUIRED BY SECTION 604.9. SECTION |
| 104.3.1.1. |
| |
| 3. A GREASE INTERCEPTOR MAY BE REQUIRED |
| AND IF SO, A GREASE WASTE SYSTEM WILL BE |
| REQUIRED FOR THE KITCHEN. PLEASE CONTACT |
| LYNN MASSON ENVIRONMENTAL COMPLIANCE FOR |
| A DERTIMINATION. HER PHONE NUMBER IS |
| (561) 822-2271, FAX (561 822-2279, AND |
| E-MAIL [email protected]. MUNICIPAL CODE |
| SECTION #3434. |
| |
| 4. THE FOLLOWING INFORMATION IS REQUIRED |
| FOR THE SEPARATE GAS PERMIT: |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. (LENGTHS FOR EACH CUT |
| SECTION NOT SHOWN). |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| (NO RESPONSE, NOT ADDRESSED). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). (NO RESPONSE, |
| NOT ADDRESSED) |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (NO |
| RESPONSE, NOT ADDRESSED). |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2. (NO |
| RESPONSE, NOT ADDRESSED). |
| J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. (NEEDS TO |
| BE SHOWN ON THE GAS RISER ISOMETRIC). |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |