Plan Review Notes
Plan Review Notes For Permit 05080175
Permit Number 05080175
Review Stop E
Sequence Number 3
Notes
Date Text
2005-12-21 00:00:00************* UNSAT ***************
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW
 STILL NEED TO BE ADDRESSED.
 PLEASE ALSO SEE CHANGES IN ELECTRICAL
 RISER ALONG WITH PLANS STILL SHOWING
 OTHER NEED TO BE ADDRESSED.
  
 *** PLEASE KNOW, WHEN PLANS WERE
 SUBMITTED BACK TO THE CONSTRUCTION
 SERVICES DEPT. ON OCT 12, 2005, "ONLY"
 THE OLD/ UN-CORRECTED PLANS WERE
 SUBMITTED BACK FOR REVIEW AND NO "NEW"
 OR REVISED PLANS WERE SUBMITTED. THIS IS
 THE REASON WHY FIRE AND ELECTRICAL
 REVIEW HAD A 2ND REVIEW WHICH REFERENCED
 TO THE SAME COMMENTS FROM ORIGINAL
 REVIEW.
 ** PLEASE KNOW THAT THE NEW/REVISED
 PLANS NOT SUBMITTED BACK ON OCT 12, WERE
 ALLOWED TO BE BROUGHT IN ON NOV 21ST,
 2005 TO BE RE-REVIEWED. THESE PLANS WERE
 BROUGHT IN BY MR. KEVIN BUTLER II.
 I HOPE THIS CLEARS UP ANY CONFUSION OVER
 WHY THERE WAS REFERENCE TO OLD/PLANS.
  
 PLEASE SEE THE FOLLOWING:
  
 ** NOTES TAKEN DIRECTLY FROM FIRST
 REVIEW.
  
 1)NOTE:NOTE #1, NO. PLEASE SEE FIRST
 PART OF NOTE MENTIONED TO SHOWALL
 CIRCUITING NEWAND CORRELATE WITH
 SUBMITTED PANEL SCHEDULE(S).
 THIS WAS DONE, HOWEVER PLEASE SEE THIS
 NOTE AND NOTE #2 REQUESTED ALLEM/EXT
 LTS TO BE CIRCUITED TO THE LOCAL BRANCH
 CIRCUIT FEEDING UNIT EQUIPMENT.THIS WAS
 DONE FOR EM LTS, HOWEVER NOT THE EXT
 LTS.
 PLEASE ADJUST CIRCUITING.
  
  
 2)NOTE: NOTE #2,YES/NO PLEASE SEE THAT
 BATTERY BACK UP EXIT LTS WERE ADDED FOR
 LIGHTING THE EGRESS PATH TO EXIT
 DISCHARGE, HOWEVER COULD NOT LCOATE ANY
 INFORMATION WITH RESPECT TO NOTES OR MIN
 FT CANDLES REQUIRED. PLEASE SEE NFPA-101
 7-8, WHICH REQUIRES THE MEANS OF EGRESS
 LIGHTING TO MEET AMIN OF 10 FT CANDLES
 DURING NORMAL POWERE AND A MIN OF 1 FT
 CANDLE DURING EMERGENCY CONDITIONS( LOSS
 OF NORMAL POWER).
 PLEASE PROVIDE AT A MININUM, NOTING FOR
 THESE MIN REQUIREMENTS.
 PLEASE SEE 2003 NFPA-101 7.8, 7.9
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK. (ONLY NOTED)
  
 6)NOTE: NOTE #6 NO, PLEASE SEE A NOTE
 WAS ADDED MENTIONING "WHEN REQUIRED"
 PLEASE SEE FIRE/MECHANCICAL REVIEW
 NOTES, A "SHUNT TRIP" OF SOME SORT WOULD
 BE REQUIRED TO SHUT DOWN ALL ELECTRICAL
 IN A HOOD AREA.
 PLEASE PROVIDE REFERENCE TO NFPA-96 WITH
 MEANS OF SHUT DOWN OF ANY
 ELECTRICAL DEVICES UNDER HOOD.
 PLEASE SEE CHAPTERS 9 AND 10
  
 7)NOTE: NOTE #7 OK, A DOOR AND WALL WERE
 ADDED TO SEPARATE FROM STORAGE AREA OF
 CLOSET.
  
 8)NOTE: NOTE #8, OK.
  
 9)NOTE: NOTE #9, NO PLEASE SEE
 250.6,250.24, "EQUIPMENT GROUNDING "
 CONDUCTORS ARE ONLY INSTALLED AFTER THE
 FIRST MEANS OF DISCONNECT.
 PLEASE SEE THESE "EQIPMENT GROUNDING
 CONDUCTORS"ARE STILL BEING SHOWN ,
 BOTH ON REFERENCE TO THE EXISTING SEC'S
 AND TO THE NEW SEC'S.
 PLEASE SEE NEW COMMENTS WITH RESPECT TO
 THE SERVICE.
 PLEASE SEE EQP GRND FROM METER TO
 MAIN.(NEW)AND EXISTING.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 NO/YES, PLEASE SEE THE
 TAPS FOR NEW MAIN IS NOW SHOWN, HOWEVER
 PLEASE SEE NEW NOTE ADDING A TAP TO
 EXISTING MAIN WILL NOT BE PERMITTED.
 PLEASE ALSO KNOW, PREVIOUS COMMENT
 REQUESTED OF THIS WAS A NEW SERVICE OR
 COMING FROM THE EXISTING SERVICE RISER?
 PLEASE SEE RISER NOW INDICATES THIS TAP
 LOCATED IN "CT" AND DOES NOT SHOW A NEW
 RISER OR SEC'S UP TO A NEW WEATHER HEAD.
 THERFORE, PLEASE SHOW EXISTING SEC'S IN
 RISER AND PLEASE BE SURE TO MAKE SURE
 THE EXISTING SIZE IS ADEQUATE FOR BOTH
 NEW AND EXISITNG. PLEASE SEE EXISITNG IS
 SHOWN AS 600A'S AND NEW MAIN IS 400'S.
 PLEASE SEE 230.2 FOR NEW
 SERVICE AS SHOWN ON PLANS. PLEASE
 CLARIFY IF "NEW SERVICE" IS GOING TO BE
 FED FROM THE SAME SERVICE DROP AND
 TRANSFORMER.
 *** PLEASE SEE PLANS STILL INDICATE
 THERE BEING A "NEW METER", AN "EXISITNG
 METER" AND AND "EXISITNG CT" WHICH DOES
 NOT CORRELATE WITH THE RISER DIAGRAM
 SHOWN FOR SERVICE.
 PLEASE CORRELATE THE ABOVE AND CALL TO
 GO OVER OPTIONS IF NEEDED.
 215.5
  
 ** NEW NOTE:
  
 1)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO THE DESIGN
 PROFESSIONAL AND REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN
 AT THIS TIME.
 ONE COPY OF ELECTRICAL PLANS ARE BEING
 RETAINED.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS ARE
 REQUIRED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-12-20 00:00:00IN ELEC FOR REVIEW.
 THIS REVIEW IS BEING DONE ON THE "NEW"
 PLANS SUBMITTED ON NOV 21ST, 2005.
  
 SOME COMMENTS FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED, AND COMMENTS DUE
 TO INFORMATION ADDED TO PLANS.
 NOTES TO FOLLOW, REVIEW IN PROGRESS.