Date |
Text |
2005-12-21 00:00:00 | ************* UNSAT *************** |
| |
| PLEASE SEE SOME NOTES FROM FIRST REVIEW |
| STILL NEED TO BE ADDRESSED. |
| PLEASE ALSO SEE CHANGES IN ELECTRICAL |
| RISER ALONG WITH PLANS STILL SHOWING |
| OTHER NEED TO BE ADDRESSED. |
| |
| *** PLEASE KNOW, WHEN PLANS WERE |
| SUBMITTED BACK TO THE CONSTRUCTION |
| SERVICES DEPT. ON OCT 12, 2005, "ONLY" |
| THE OLD/ UN-CORRECTED PLANS WERE |
| SUBMITTED BACK FOR REVIEW AND NO "NEW" |
| OR REVISED PLANS WERE SUBMITTED. THIS IS |
| THE REASON WHY FIRE AND ELECTRICAL |
| REVIEW HAD A 2ND REVIEW WHICH REFERENCED |
| TO THE SAME COMMENTS FROM ORIGINAL |
| REVIEW. |
| ** PLEASE KNOW THAT THE NEW/REVISED |
| PLANS NOT SUBMITTED BACK ON OCT 12, WERE |
| ALLOWED TO BE BROUGHT IN ON NOV 21ST, |
| 2005 TO BE RE-REVIEWED. THESE PLANS WERE |
| BROUGHT IN BY MR. KEVIN BUTLER II. |
| I HOPE THIS CLEARS UP ANY CONFUSION OVER |
| WHY THERE WAS REFERENCE TO OLD/PLANS. |
| |
| PLEASE SEE THE FOLLOWING: |
| |
| ** NOTES TAKEN DIRECTLY FROM FIRST |
| REVIEW. |
| |
| 1)NOTE:NOTE #1, NO. PLEASE SEE FIRST |
| PART OF NOTE MENTIONED TO SHOWALL |
| CIRCUITING NEWAND CORRELATE WITH |
| SUBMITTED PANEL SCHEDULE(S). |
| THIS WAS DONE, HOWEVER PLEASE SEE THIS |
| NOTE AND NOTE #2 REQUESTED ALLEM/EXT |
| LTS TO BE CIRCUITED TO THE LOCAL BRANCH |
| CIRCUIT FEEDING UNIT EQUIPMENT.THIS WAS |
| DONE FOR EM LTS, HOWEVER NOT THE EXT |
| LTS. |
| PLEASE ADJUST CIRCUITING. |
| |
| |
| 2)NOTE: NOTE #2,YES/NO PLEASE SEE THAT |
| BATTERY BACK UP EXIT LTS WERE ADDED FOR |
| LIGHTING THE EGRESS PATH TO EXIT |
| DISCHARGE, HOWEVER COULD NOT LCOATE ANY |
| INFORMATION WITH RESPECT TO NOTES OR MIN |
| FT CANDLES REQUIRED. PLEASE SEE NFPA-101 |
| 7-8, WHICH REQUIRES THE MEANS OF EGRESS |
| LIGHTING TO MEET AMIN OF 10 FT CANDLES |
| DURING NORMAL POWERE AND A MIN OF 1 FT |
| CANDLE DURING EMERGENCY CONDITIONS( LOSS |
| OF NORMAL POWER). |
| PLEASE PROVIDE AT A MININUM, NOTING FOR |
| THESE MIN REQUIREMENTS. |
| PLEASE SEE 2003 NFPA-101 7.8, 7.9 |
| |
| 3)NOTE: NOTE #3 OK. |
| |
| 4)NOTE: NOTE #4 OK. |
| |
| 5)NOTE: NOTE #5 OK. (ONLY NOTED) |
| |
| 6)NOTE: NOTE #6 NO, PLEASE SEE A NOTE |
| WAS ADDED MENTIONING "WHEN REQUIRED" |
| PLEASE SEE FIRE/MECHANCICAL REVIEW |
| NOTES, A "SHUNT TRIP" OF SOME SORT WOULD |
| BE REQUIRED TO SHUT DOWN ALL ELECTRICAL |
| IN A HOOD AREA. |
| PLEASE PROVIDE REFERENCE TO NFPA-96 WITH |
| MEANS OF SHUT DOWN OF ANY |
| ELECTRICAL DEVICES UNDER HOOD. |
| PLEASE SEE CHAPTERS 9 AND 10 |
| |
| 7)NOTE: NOTE #7 OK, A DOOR AND WALL WERE |
| ADDED TO SEPARATE FROM STORAGE AREA OF |
| CLOSET. |
| |
| 8)NOTE: NOTE #8, OK. |
| |
| 9)NOTE: NOTE #9, NO PLEASE SEE |
| 250.6,250.24, "EQUIPMENT GROUNDING " |
| CONDUCTORS ARE ONLY INSTALLED AFTER THE |
| FIRST MEANS OF DISCONNECT. |
| PLEASE SEE THESE "EQIPMENT GROUNDING |
| CONDUCTORS"ARE STILL BEING SHOWN , |
| BOTH ON REFERENCE TO THE EXISTING SEC'S |
| AND TO THE NEW SEC'S. |
| PLEASE SEE NEW COMMENTS WITH RESPECT TO |
| THE SERVICE. |
| PLEASE SEE EQP GRND FROM METER TO |
| MAIN.(NEW)AND EXISTING. |
| |
| 10)NOTE: NOTE #10 OK. |
| |
| 11)NOTE: NOTE #11 NO/YES, PLEASE SEE THE |
| TAPS FOR NEW MAIN IS NOW SHOWN, HOWEVER |
| PLEASE SEE NEW NOTE ADDING A TAP TO |
| EXISTING MAIN WILL NOT BE PERMITTED. |
| PLEASE ALSO KNOW, PREVIOUS COMMENT |
| REQUESTED OF THIS WAS A NEW SERVICE OR |
| COMING FROM THE EXISTING SERVICE RISER? |
| PLEASE SEE RISER NOW INDICATES THIS TAP |
| LOCATED IN "CT" AND DOES NOT SHOW A NEW |
| RISER OR SEC'S UP TO A NEW WEATHER HEAD. |
| THERFORE, PLEASE SHOW EXISTING SEC'S IN |
| RISER AND PLEASE BE SURE TO MAKE SURE |
| THE EXISTING SIZE IS ADEQUATE FOR BOTH |
| NEW AND EXISITNG. PLEASE SEE EXISITNG IS |
| SHOWN AS 600A'S AND NEW MAIN IS 400'S. |
| PLEASE SEE 230.2 FOR NEW |
| SERVICE AS SHOWN ON PLANS. PLEASE |
| CLARIFY IF "NEW SERVICE" IS GOING TO BE |
| FED FROM THE SAME SERVICE DROP AND |
| TRANSFORMER. |
| *** PLEASE SEE PLANS STILL INDICATE |
| THERE BEING A "NEW METER", AN "EXISITNG |
| METER" AND AND "EXISITNG CT" WHICH DOES |
| NOT CORRELATE WITH THE RISER DIAGRAM |
| SHOWN FOR SERVICE. |
| PLEASE CORRELATE THE ABOVE AND CALL TO |
| GO OVER OPTIONS IF NEEDED. |
| 215.5 |
| |
| ** NEW NOTE: |
| |
| 1)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO THE DESIGN |
| PROFESSIONAL AND REPEAT COMMENTS FOR |
| CODE COMPLIANCE. |
| PLEASE KNOW THIS IS ONLY A NOTICE GIVEN |
| AT THIS TIME. |
| ONE COPY OF ELECTRICAL PLANS ARE BEING |
| RETAINED. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD/VOIDED SHEETS ARE |
| REQUIRED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
2005-12-20 00:00:00 | IN ELEC FOR REVIEW. |
| THIS REVIEW IS BEING DONE ON THE "NEW" |
| PLANS SUBMITTED ON NOV 21ST, 2005. |
| |
| SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| NEED TO BE ADDRESSED, AND COMMENTS DUE |
| TO INFORMATION ADDED TO PLANS. |
| NOTES TO FOLLOW, REVIEW IN PROGRESS. |