Date |
Text |
2006-01-31 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 FUEL GAS |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| A. PREVIOUS COMMENTS FROM FIRST REVIEW |
| NOT ADDRESSED. COMMENT NUMBERS TO REMAIN |
| THE SAME AS FIRST REVIEW: |
| |
| 1. INDICATE AGE OF STUDENTS TO DETERMINE |
| THE OCCUPANCY. SECTION 104.2.1. (NOT |
| ADDRESSED, NO RESPONSE). PLEASE INDICATE |
| OCCUPANCY AND INDICATE AGE OF STUDENTS. |
| 2. ROUTE PLANS TO THE PALM BEACH HEALTH |
| UNIT DIVISION OF ENVIRONMENTAL HEALTH |
| FOR REVIEW PRIOR TO RESUBMITTING FOR |
| PLAN REVIEW AT THE CITY WPB. SECTION |
| 101.4.7. (NO RESPONSE, NOT ADDRESSED). |
| 4. SHT A-6 SHOW THE FOLLOWING TO SHOW |
| COMPLIANCE OF THE ACCESSIBILITY CODE: |
| FOR LAVS... |
| 11-4.19.5 FAUCETS |
| TOILET ROOM: |
| 11-4.22.3 TURNING AREA IN TOILET ROOM, |
| NOT IN THE STALL. |
| 5. SHT P-1 IF THE DESIGN PROFESSIONAL IS |
| AN ARCHITECT OR ENGINEER LEGALLY |
| REGISTERED UNDER THE LAWS OF THIS STATE |
| REGULATING THE PRACTICE OF ARCHITECTURE |
| OR ENGINEERING, THEN HE/SHE SHALL AFFIX |
| HIS/HER OFFICIAL SEAL TO SAID DRAWINGS, |
| AS REQUIRED FY FLORIDA STATUTES. SECTION |
| 104.2.2. (SHEETS A-1, A-4,A-7, & S-1 NOT |
| SIGNED, SEALED, DATED) |
| 8. THE FOLLOWING INFORMATION IS REQUIRED |
| FOR THE SEPARATE GAS PERMIT: |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2001 |
| FUEL GAS CODE. (LENGTHS FOR EACH CUT |
| SECTION NOT SHOWN). |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| (NO RESPONSE, NOT ADDRESSED). |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES (A)(3). (NO RESPONSE, |
| NOT ADDRESSED) |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2001 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (NO |
| RESPONSE, NOT ADDRESSED). |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2001 FUEL GAS CODE SEC 402.2. (NO |
| RESPONSE, NOT ADDRESSED). |
| J. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. (NEEDS TO |
| BE SHOWN ON THE GAS RISER ISOMETRIC). |
| |
| **************NEW COMMENT*************** |
| 1B. SEE ATTACHED SHEET CONCERNING FS |
| 553.80(2)(B) AND THE DESIGN |
| PROFESSIONAL. (ATTACHED TO ELECTRICAL |
| COMMENTS). THIS IS GIVEN AS A NOTICE. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |