Plan Review Notes
Plan Review Notes For Permit 05080175
Permit Number 05080175
Review Stop P
Sequence Number 2
Notes
Date Text
2006-01-31 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 A. PREVIOUS COMMENTS FROM FIRST REVIEW
 NOT ADDRESSED. COMMENT NUMBERS TO REMAIN
 THE SAME AS FIRST REVIEW:
  
 1. INDICATE AGE OF STUDENTS TO DETERMINE
 THE OCCUPANCY. SECTION 104.2.1. (NOT
 ADDRESSED, NO RESPONSE). PLEASE INDICATE
 OCCUPANCY AND INDICATE AGE OF STUDENTS.
 2. ROUTE PLANS TO THE PALM BEACH HEALTH
 UNIT DIVISION OF ENVIRONMENTAL HEALTH
 FOR REVIEW PRIOR TO RESUBMITTING FOR
 PLAN REVIEW AT THE CITY WPB. SECTION
 101.4.7. (NO RESPONSE, NOT ADDRESSED).
 4. SHT A-6 SHOW THE FOLLOWING TO SHOW
 COMPLIANCE OF THE ACCESSIBILITY CODE:
 FOR LAVS...
 11-4.19.5 FAUCETS
 TOILET ROOM:
 11-4.22.3 TURNING AREA IN TOILET ROOM,
 NOT IN THE STALL.
 5. SHT P-1 IF THE DESIGN PROFESSIONAL IS
 AN ARCHITECT OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE
 OR ENGINEERING, THEN HE/SHE SHALL AFFIX
 HIS/HER OFFICIAL SEAL TO SAID DRAWINGS,
 AS REQUIRED FY FLORIDA STATUTES. SECTION
 104.2.2. (SHEETS A-1, A-4,A-7, & S-1 NOT
 SIGNED, SEALED, DATED)
 8. THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. (LENGTHS FOR EACH CUT
 SECTION NOT SHOWN).
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 (NO RESPONSE, NOT ADDRESSED).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). (NO RESPONSE,
 NOT ADDRESSED)
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. (NO
 RESPONSE, NOT ADDRESSED).
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2. (NO
 RESPONSE, NOT ADDRESSED).
 J. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (NEEDS TO
 BE SHOWN ON THE GAS RISER ISOMETRIC).
  
 **************NEW COMMENT***************
 1B. SEE ATTACHED SHEET CONCERNING FS
 553.80(2)(B) AND THE DESIGN
 PROFESSIONAL. (ATTACHED TO ELECTRICAL
 COMMENTS). THIS IS GIVEN AS A NOTICE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved