2005-12-25 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2001 |
| |
| |
| 1.)FROM PREVIOUS REVIEW, #4.PROVIDE |
| INFORMATION IN REGARDS TO |
| THE EXISTING BUILDING; MINIMUM BUILDING |
| TYPE, HEIGHT (NUMBER OF STORIES), |
| PROTECTED OR UNPROTECTED, SPRINKLED OR |
| UNSPRINKLED, OCCUPANCY SO THAT FBC TABLE |
| 500 COMPLIANCE CAN BE DETERMINED. |
| |
| PLEASE PROVIDE ALL INFORMATION |
| REQUESTED.SHOW COMPLIANCE WITH FBC |
| TABLE 500 AS REQUESTED ON FIRST REVIEW. |
| THIS IS TYPICALLY DONE IN A CODE SUMMARY |
| SECTION.SOME INFORMATION WAS PROVIDED |
| BUT NOT ENOUGH TO DETERMINE CODE |
| COMPLIANCE.FOR INSTANCE, WHETHER OR |
| NOT THE BUILDING IS SPRINKLED WAS NOT |
| DECLARED ON THE PLAN.THE OCCUPANCY |
| CLASSIFICATION AND SUBCLASSIFICATION WAS |
| NOT DECLARED, PROTECTED OR UNPROTECTED. |
| IT APPEARS TO BE ONE STORY, PLEASE |
| DECLARE SO ON THE PLAN. |
| |
| 2.)SEE FBC503.1.2.YOU SHOW A PORTION |
| OF THE BUILDING AS TYPE V, ANOTHER |
| PORTION AS TYPE III.FOR A BUILDING TO |
| BE DECLARED TWO DIFFERENT BUILDING |
| TYPES, A FIRE WALL BETWEEN THE TWO |
| BUILDING TYPES IS REQUIRED.SHOW |
| EXISTING OR PROPOSED FIRE WALL AND |
| PROVIDE A DETAIL.PROVIDE INFORMATION |
| IN REGARDS TO EXISTING CONSTRUCTION SO |
| THAT THE BUILDING TYPE DECLARED CAN BE |
| CONFIRMED. |
| |
| 3.)IF THIS IS TWO BUILDINGS AS DEFINED |
| BY FBC503.1.2, PROVIDE TOTAL AREA OF |
| EACH BUILDING TYPE SO THAT TABLE 500 |
| COMPLIANCE CAN BE DETERMINED. |
| |
| 4.)IF THIS ENTIRE BUILDING IS ACTUALLY |
| A TYPE V BUILDING, SEE FBC TABLE 500. |
| AN UNSPRINKLED TYPE V A2 BUILDING IS |
| RESTRICTED TO A SIZE OF 8000 SF.THIS |
| BUILDING IS OVER 13,000 AND YOU ARE |
| PROPOSING TO ADD 200 SF.THE ADDITION |
| AS PRESENTED DOES NOT APPEAR CODE |
| COMPLIANT BUT NOT ENOUGH INFORMATION WAS |
| PROVIDED TO MAKE THIS DETERMINATION. |
| |
| 5.)DECLARE GOVERNING CODE.IF YOU ARE |
| DESIGNING UNDER THE FBC2004, PLEASE |
| ADVISE SO THAT I CAN REVISE CODE |
| REFERENCE NUMBERS IF NECESSARY. |
| COMMENTS STILL APPLY. |
| |
| 6.)IF YOU ARE DESIGNING UNDER FBC2004, |
| PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| THE DESIGNER OF RECORD, CITY OF WEST |
| PALM BEACH AMENDMENTS TO THE FBC2004 |
| 106.3.3. |
| |
| 7.)FROM PREVIOUS REVIEW, ITEM #8. |
| FLORIDA STATE OR LOCAL PRODUCT APPROVALS |
| REQUIRED FOR THE ROOF AND THE WINDOW. |
| PROVIDE BOTH THE STATE OR LOCAL PRODUCT |
| APPROVAL AND THE CORRESPONDING |
| EVALUATION OR TEST REPORT AND |
| INSTALLATION INSTRUCTIONS.THE |
| RESPONSE LETTER FROM THE ARCHITECT |
| STATES THAT THE WINDOWS ARE EXISTING AND |
| NOT BEING REPLACED.THERE IS A NEW |
| WINDOW SHOWN AT THE SINK IN THE KITCHEN |
| ADDITION.PRODUCT APPROVAL FOR THE ROOF |
| WERE NOT SUBMITTED. |
| |
| WWW.FLORIDABUILDING.ORG |
| |
| 7.)IMPACT PROTECTION REQUIRED FOR THE |
| WINDOW FBC1606.1.4.IF YOU PROPOSE |
| USING REMOVABLE SHUTTERS, APPROVAL BY |
| THE BUILDING OFFICIAL IS REQUIRED.SEE |
| ATTACHED POLICY, ITEM 13. |
| |
| 8.)SHEETS A1, A4, A7, S1 ARE NOT |
| SEALED.DOCUMENTS PREPARED BY AN |
| ARCHITECT AND SUBMITTED FOR PUBLIC |
| RECORD ARE TO BE SIGNED, SEALED, AND |
| DATED ORIGINALS.FAC61G1-16. |
| |
| 9.)THE NOA SUBMITTED IS EXPIRED, OVER |
| 90 DAYS WITHOUT COMMENCING WORK, |
| FS713.13(2). |
| |
| 10.) SHOW TURNING RADIUS IN BATHROOM, |
| FBC11-4.22.3. |
| |
| 11.) SPECIFY HURRICANE STRAPS AND SHOW |
| DESIGN CRITERIA, SHEET A7. |
| |
| 12.) SEE ATTACHED FS553.80(2)(B).A 4X |
| PLAN REVIEW IS REQUIRED TO BE CHARGED IF |
| THE CORRECTIONS ARE NOT PROPERLY |
| ADDRESSED IN THE THIRD REVIEW. |