Plan Review Notes
Plan Review Notes For Permit 05080175
Permit Number 05080175
Review Stop B
Sequence Number 2
Notes
Date Text
2005-12-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
  
 1.)FROM PREVIOUS REVIEW, #4.PROVIDE
 INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; MINIMUM BUILDING
 TYPE, HEIGHT (NUMBER OF STORIES),
 PROTECTED OR UNPROTECTED, SPRINKLED OR
 UNSPRINKLED, OCCUPANCY SO THAT FBC TABLE
 500 COMPLIANCE CAN BE DETERMINED.
  
 PLEASE PROVIDE ALL INFORMATION
 REQUESTED.SHOW COMPLIANCE WITH FBC
 TABLE 500 AS REQUESTED ON FIRST REVIEW.
 THIS IS TYPICALLY DONE IN A CODE SUMMARY
 SECTION.SOME INFORMATION WAS PROVIDED
 BUT NOT ENOUGH TO DETERMINE CODE
 COMPLIANCE.FOR INSTANCE, WHETHER OR
 NOT THE BUILDING IS SPRINKLED WAS NOT
 DECLARED ON THE PLAN.THE OCCUPANCY
 CLASSIFICATION AND SUBCLASSIFICATION WAS
 NOT DECLARED, PROTECTED OR UNPROTECTED.
 IT APPEARS TO BE ONE STORY, PLEASE
 DECLARE SO ON THE PLAN.
  
 2.)SEE FBC503.1.2.YOU SHOW A PORTION
 OF THE BUILDING AS TYPE V, ANOTHER
 PORTION AS TYPE III.FOR A BUILDING TO
 BE DECLARED TWO DIFFERENT BUILDING
 TYPES, A FIRE WALL BETWEEN THE TWO
 BUILDING TYPES IS REQUIRED.SHOW
 EXISTING OR PROPOSED FIRE WALL AND
 PROVIDE A DETAIL.PROVIDE INFORMATION
 IN REGARDS TO EXISTING CONSTRUCTION SO
 THAT THE BUILDING TYPE DECLARED CAN BE
 CONFIRMED.
  
 3.)IF THIS IS TWO BUILDINGS AS DEFINED
 BY FBC503.1.2, PROVIDE TOTAL AREA OF
 EACH BUILDING TYPE SO THAT TABLE 500
 COMPLIANCE CAN BE DETERMINED.
  
 4.)IF THIS ENTIRE BUILDING IS ACTUALLY
 A TYPE V BUILDING, SEE FBC TABLE 500.
 AN UNSPRINKLED TYPE V A2 BUILDING IS
 RESTRICTED TO A SIZE OF 8000 SF.THIS
 BUILDING IS OVER 13,000 AND YOU ARE
 PROPOSING TO ADD 200 SF.THE ADDITION
 AS PRESENTED DOES NOT APPEAR CODE
 COMPLIANT BUT NOT ENOUGH INFORMATION WAS
 PROVIDED TO MAKE THIS DETERMINATION.
  
 5.)DECLARE GOVERNING CODE.IF YOU ARE
 DESIGNING UNDER THE FBC2004, PLEASE
 ADVISE SO THAT I CAN REVISE CODE
 REFERENCE NUMBERS IF NECESSARY.
 COMMENTS STILL APPLY.
  
 6.)IF YOU ARE DESIGNING UNDER FBC2004,
 PRODUCT APPROVALS ARE TO BE REVIEWED BY
 THE DESIGNER OF RECORD, CITY OF WEST
 PALM BEACH AMENDMENTS TO THE FBC2004
 106.3.3.
  
 7.)FROM PREVIOUS REVIEW, ITEM #8.
 FLORIDA STATE OR LOCAL PRODUCT APPROVALS
 REQUIRED FOR THE ROOF AND THE WINDOW.
 PROVIDE BOTH THE STATE OR LOCAL PRODUCT
 APPROVAL AND THE CORRESPONDING
 EVALUATION OR TEST REPORT AND
 INSTALLATION INSTRUCTIONS.THE
 RESPONSE LETTER FROM THE ARCHITECT
 STATES THAT THE WINDOWS ARE EXISTING AND
 NOT BEING REPLACED.THERE IS A NEW
 WINDOW SHOWN AT THE SINK IN THE KITCHEN
 ADDITION.PRODUCT APPROVAL FOR THE ROOF
 WERE NOT SUBMITTED.
  
 WWW.FLORIDABUILDING.ORG
  
 7.)IMPACT PROTECTION REQUIRED FOR THE
 WINDOW FBC1606.1.4.IF YOU PROPOSE
 USING REMOVABLE SHUTTERS, APPROVAL BY
 THE BUILDING OFFICIAL IS REQUIRED.SEE
 ATTACHED POLICY, ITEM 13.
  
 8.)SHEETS A1, A4, A7, S1 ARE NOT
 SEALED.DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED, SEALED, AND
 DATED ORIGINALS.FAC61G1-16.
  
 9.)THE NOA SUBMITTED IS EXPIRED, OVER
 90 DAYS WITHOUT COMMENCING WORK,
 FS713.13(2).
  
 10.) SHOW TURNING RADIUS IN BATHROOM,
 FBC11-4.22.3.
  
 11.) SPECIFY HURRICANE STRAPS AND SHOW
 DESIGN CRITERIA, SHEET A7.
  
 12.) SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW IS REQUIRED TO BE CHARGED IF
 THE CORRECTIONS ARE NOT PROPERLY
 ADDRESSED IN THE THIRD REVIEW.