2006-12-09 17:00:44REDLINED E-2 AGAIN FOR THE MINIMUM SIZE FOR THE GEC AS
 STATED AND REDLINED ON PREVIOUS PLANS. NEEDS TO BE A
 2/0 MIN PER 250.66 AND THE SEC'S SHOWN ON RISER.