Plan Review Notes
Plan Review Notes For Permit 05080175
Permit Number 05080175
Review Stop P
Sequence Number 1
Notes
Date Text
2005-09-07 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
  
 1. INDICATE AGE OF STUDENTS TO DETERMINE
 THE OCCUPANCY. SECTION 104.2.1.
 2. ROUTE PLANS TO THE PALM BEACH HEALTH
 UNIT DIVISION OF ENVIRONMENTAL HEALTH
 FOR REVIEW PRIOR TO RESUBMITTING FOR
 PLAN REVIEW AT THE CITY WPB. SECTION
 101.4.7.
 3. MINIMUM FACILITIES REQUIRE A DRINKING
 FOUNTAIN AND A SERVICE SINK PER TABLE
 403.1.
 4. SHT A-6 SHOW THE FOLLOWING TO SHOW
 COMPLIANCE OF THE ACCESSIBILITY CODE:
 FOR W/C'S..
 11-4.16.2 CLEAR FLOOR SPACE
 11-4.16.3 HEIGHT
 11-4.16.5 FLUSH CONTROLS
 FOR UNINAL..
 11.4.18.2 HEIGHT
 11-4.18.3 CLEAR FLOOR SPACE
 11-4.18.4 FLUSH CONTROLS
 FOR LAVS...
 11-4.19.2 HEIGHT & CLEARANCES -
 INCLUDING LAV OUTSIDE ACCESSIBLE STALL.
 11-4.19.3 CLEAR FLOOR SPACE
 11-4.19.4 EXPOSED PIPES & SURFACES
 11-4.19.5 FAUCETS
 TOILET ROOM:
 11-4.22.3 TURNING AREA IN TOILET ROOM,
 NOT IN THE STALL.
 5. SHT P-1 IF THE DESIGN PROFESSIONAL IS
 AN ARCHITECT OR ENGINEER LEGALLY
 REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ARCHITECTURE
 OR ENGINEERING, THEN HE/SHE SHALL AFFIX
 HIS/HER OFFICIAL SEAL TO SAID DRAWINGS,
 AS REQUIRED FY FLORIDA STATUTES. SECTION
 104.2.2.
 6. SHT P-1 SANT RISER DIAGRAM, SHOW ALL
 PIPE SIZES, CLEANOUTS REQUIRED BY
 SECTION 708.3.3, (AT CHANGE OF
 DIRECTION), VENTS ECT. SECTIONS 104.2.1
 & SECTION 901.2.1. - IF SINKS ARE IN THE
 FOOD PREPARATION AREA THEN THE SINKS
 SHALL DRAIN INDIRECTLY INTO A FLOOR SINK
 PER SECTION 802.3.
 7. SHT P-1 WATER RISER DIAGRAM, SHOW ALL
 PIPE SIZES, VALVES AND WATER HAMMER
 ARRESTORS IF REQUIRED BY SECTION 604.9,
 (QUICK CLOSING VALVES).
 8. THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE SEPARATE GAS PERMIT:
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 C. TYPE OF GAS, (LP OR NATURAL)
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 I. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  