Plan Review Notes For Permit 05080175 |
Permit Number |
05080175 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-08 00:00:00 | DENIED: | | 1.PROVIDE OUTSIDE AIR CALCULATIONS IN | | ACCORDANCE WITH 2001 FBC(M) TABLE 403.3. | | | | 2.PLEASE INDICATE TYPE OF VENT TO THE | | WATER HEATER. REFERENCE 2001 FBC(F) | | CHAPTER 5.PROVIDE MANUFACTURER'S | | INSTALLATION INFORMATION. | | | | 3.PLAN SHEET M-2 HVAC GENERAL NOTE #17 | | INDICATES HOOD FOR THE GAS STOVE. | | PLEASE NOTE, SEPARATE PERMIT REQUIRED | | FOR HOOD & SUPPRESSION.PLEASE PROVIDE | | PLANS AND MANUFACTURER'S SPECIFICATIONS | | FOR THE HOOD.HOOD & GREASE DUCT SHALL | | COMPLY WITH 2001 FBC(M) 507 & 506 | | RESPECTIVELY. | | | | 4.CONDENSATE SHALL TERMINATE IN | | ACCORDANCE WITH 2001 FBC(M)307.2.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|