2005-08-15 00:00:00 | ********* UNSAT ********* |
| |
| 1)NOTE: PLEASE SHOW ALL CIRCUITING FOR |
| NEWAND CORRELATE WITH SUBMITTED PANEL |
| SCHEDULE(S). |
| PLEASE SEE EXT/ EM LT PER 700.12E,THE |
| BRANCH |
| CIRCUIT FEEDING THE UNIT EQUIPMENT SHALL |
| BE THE SAME BRANCH CIRCUIT AS THAT |
| SERVING THE NORMAL LIGHTING IN THE AREA |
| AND CONNECTED AHEAD OF ANY LOCAL |
| SWITCHES. |
| |
| |
| 2)NOTE: PLEASE SEE NFPA-101 7-8, WHICH |
| REQUIRES MEANS OF EGRESS LIGHTING TO THE |
| EXIT DISCHARGE/ TO PUBLIC RIGHT OF WAY. |
| PLEASE SEE CORRIDORS IN OPEN COURTYARD |
| AREAS. 101,15.2 |
| PLEASE ALSO SEE 700.12E FOR CIRCUITINGOF |
| EM/LTS.PREVIOUSLY NOTED. |
| |
| 3)NOTE: PLEASE SEE 2002 NEC FOR |
| PROTECTION OF RECEPTS IN KITCHENS IN |
| OTHER THAN DWELLING UNITS, WHICH |
| REQUIRES ALL 15- AND 20-AMPERE, 125-VOLT |
| RECEPTACLES IN NONDWELLING-TYPE KITCHENS |
| TO BE GFCI PROTECTED. THIS REQUIREMENT |
| APPLIES TO EACH AND EVERY 15- AND |
| 20-AMPERE, 125-VOLT KITCHEN RECEPTACLE, |
| WHETHER OR NOT THE RECEPTACLE SERVES |
| COUNTERTOP APPLIANCES. |
| |
| 4)NOTE: PLEASE SEE MISSING THE "PRINTED" |
| LICENSE NUMBER OF THE ENGINEER OF |
| RECORD. PLEASE SEE FAC 61G15-23.002 |
| FS 471 |
| |
| 5)NOTE: PLEASE SEE BLDG, ZOING COMMENTS, |
| NO SURVEY/SITE PLAN SHOWING SETBACKS FOR |
| NEW KITCHAN ADDITION WAS SUBMITTED. |
| PLEASE SEE FS 472.025, FAC 61G17-7.002, |
| PLEASE BE SURE ALL SURVEY'S CONTAIN THE |
| ABOVE. |
| |
| 6)NOTE: PLEASE PROVIDE REFERENCE TO |
| NFPA-96 WITH MEANS OF SHUT DOWN OF ANY |
| ELECTRICAL DEVICES UNDER HOOD. |
| PLEASE SEE CHAPTERS 9 AND 10 |
| |
| 7)NOTE: PLEASE SEE PANEL "B" WHICH IS |
| SHOWN AS EXISTING SHALL NOT BE LOCATED |
| IN "OFFICE CLOSET". PLEASE SEE FIRE |
| REVIEW NOTES, NO STORAGE PERMITTED IN |
| SPACES ABOUT ELECTRICAL EQUIPMENT/RMS. |
| PLEASE SEE 408.7,240.24D, 110.26 ETC |
| PLEASE SEE THIS AREA FOR LOCATION OF |
| PANEL NEEDS TO REFERENCE, ELEC/MECH RM. |
| |
| 8)NOTE:PLEASE CLARIFY/ SHOW EITHER NEW |
| OR EXISTING ROOF-TOP WP GFI RECEPTS FOR |
| RTU'S PER 210.63 |
| |
| 9)NOTE: PLEASE SEE 250.6,250.24, |
| "EQUIPMENT GROUNDING " CONDUCTORS ARE |
| ONLY INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| PLEASE SEE EQP GRND FROM METER TO |
| MAIN.(NEW). |
| |
| 10)NOTE: PLEASE SHOW METHOD OF EQUIPMENT |
| GROUNDING FROM PANELS TO ALL RTU'S. |
| PLEASE KNOW, EMT MAY ONLY BE USED AS AN |
| "EQUIPMENT GROUND PATH" IF USED IN |
| CONNECTION WITH NEW "LISTED" EQUIPMENT |
| GROUNDING CONNECTORS AND COUPLINGS. |
| 110.3 |
| |
| 11)NOTE: PLEASE SEE 230.2 FOR NEW |
| SERVICE AS SHOWN ON PLANS. PLEASE |
| CLARIFY IF "NEW SERVICE" IS GOING TO BE |
| FED FROM THE SAME SERVICE DROP AND |
| TRANSFORMER. |
| 215.3 |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD/VOIDED SHEETS ARE |
| REQUIRED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |