Plan Review Notes
Plan Review Notes For Permit 05080175
Permit Number 05080175
Review Stop B
Sequence Number 1
Notes
Date Text
2005-08-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 2.)THIS IS AN OVER 50% IMPROVEMENT
 FBC3401.7.2.6 (SEE PROPERTY APPRAISER
 VALUATION).SOME COMMENTS MAY RELATE TO
 THIS CODE SECTION.
  
 3.)PROVIDE AREA CALCULATIONS ?
 EXISTING, PROPOSED, NEW TOTAL.
  
 4.)PROVIDE INFORMATION IN REGARDS TO
 THE EXISTING BUILDING; MINIMUM BUILDING
 TYPE, HEIGHT (NUMBER OF STORIES),
 PROTECTED OR UNPROTECTED, SPRINKLED OR
 UNSPRINKLED, OCCUPANCY SO THAT FBC TABLE
 500 COMPLIANCE CAN BE DETERMINED.
  
 5.)SPECIFY MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR THE DECLARED
 OCCUPANCY, FBC TABLE 803.3.
  
 6.)MEANS OF EGRESS SHALL BE TO THE
 EXTERIOR OF THE BUILDING, FBC1001.3.
 EXIT LIGHTS ARE REQUIRED AT THE GATES
 LEADING OUTSIDE THE COVERED AREAS.
  
 7.)THE TITLE BLOCK FOR THE ENGINEER IS
 TO CONTAIN ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 (PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT).
  
 8.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVALS REQUIRED FOR:
  
 ROOF
 WINDOW
  
 WWW.FLORIDABUILDING.ORG
  