Plan Review Notes For Permit 05080141 |
Permit Number |
05080141 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-08-17 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05080141 | | ADD: 1555 PALM BEACH LAKES BLVD | | CONT:ANDREW'S ROOFING | | TEL: (561) 688-1066 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) THIS BUILDING IS A HIGH RISE! PROVIDE | | A SITE PLAN INDICATING WHERE ON THIS | | BUILDING THIS SYSTEM IS TO BE USED. | | | | 2) FROM PREVIOUS REVIEW, SPECIFY THE | | DECK MATERIAL, ANSWER IS " 5/8" CDX | | PLYWOOD SHEATHING BY OTHERS OVER | | EXISTING, NO PERMIT HAS BEEN APPPLIED | | FOR FOR THIS WORK. PROVIDE WHERE THIS | | WORK IS TO OCCUR, THIS IS A TYPEII | | BUILDING WHERE NO PLYWOODSHEATHING IS TO | | BE USED. IS THIS THE AREA OF GREENHOUSE | | LOCATED ON THE FIRST FLOOR? IF SO WHAT | | MATERIAL WIL MAKE UP THE ROOF DECK? | | | | 3) THIS BUILDING BEING A HIGH RISE THE | | NEGATIVE PRESSURES ARE TAKEN FROM THE | | ROOF HEIGHT, ENGINEERED SYSTEM SHOWING | | ZONES 1,2 & 3. | | | | 4) SINCE THIS BUILDING REQUIRES A 1HR | | RATED ROOF ASSEMBLY PROVIDE HOW THIS | | COMPLIANCE WILLBE ACHIEVED. | | | | 5)THE SUBMITTED ROOF REPORT HAS LOW | | PRESSURES FOR END ZONE. TO BE AN | | ENGINEERED SYSTEM. | | | | 6) 1507.5 METAL ROOF PANELS SLOPE | | MINIMUM OF A 3:12 SLOPE. | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | | | | | |
|