2005-08-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05080141
 ADD: 1555 PALM BEACH LAKES BLVD
 CONT:ANDREW'S ROOFING
 TEL: (561) 688-1066
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THIS BUILDING IS A HIGH RISE! PROVIDE
 A SITE PLAN INDICATING WHERE ON THIS
 BUILDING THIS SYSTEM IS TO BE USED.
  
 2) FROM PREVIOUS REVIEW, SPECIFY THE
 DECK MATERIAL, ANSWER IS " 5/8" CDX
 PLYWOOD SHEATHING BY OTHERS OVER
 EXISTING, NO PERMIT HAS BEEN APPPLIED
 FOR FOR THIS WORK. PROVIDE WHERE THIS
 WORK IS TO OCCUR, THIS IS A TYPEII
 BUILDING WHERE NO PLYWOODSHEATHING IS TO
 BE USED. IS THIS THE AREA OF GREENHOUSE
 LOCATED ON THE FIRST FLOOR? IF SO WHAT
 MATERIAL WIL MAKE UP THE ROOF DECK?
  
 3) THIS BUILDING BEING A HIGH RISE THE
 NEGATIVE PRESSURES ARE TAKEN FROM THE
 ROOF HEIGHT, ENGINEERED SYSTEM SHOWING
 ZONES 1,2 & 3.
  
 4) SINCE THIS BUILDING REQUIRES A 1HR
 RATED ROOF ASSEMBLY PROVIDE HOW THIS
 COMPLIANCE WILLBE ACHIEVED.
  
 5)THE SUBMITTED ROOF REPORT HAS LOW
 PRESSURES FOR END ZONE. TO BE AN
 ENGINEERED SYSTEM.
  
 6) 1507.5 METAL ROOF PANELS SLOPE
 MINIMUM OF A 3:12 SLOPE.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  