2005-08-03 00:00:00DENIED
  
 1) SPECIFY WHICH ONE OF THE APPROVED
 ASSEMBLIES FROM THE PRODUCT APPROVAL
 WILL BE INSTALLED.
  
 2) SPECIFY THE MEAN ROOF HEIGHT OF THE
 STRUCTURE.
  
 3) SPECIFY THE DECK MATERIAL.
  
 4) ROOF PITCH SPECIFIED ON THE
 APPLICATION IS 1:12, THE MINIMUM SLOPE
 ALLOWED FOR THIS PRODUCT IS 2:12.
  
 5) SUBMIT SIGNED AND SEALED CALCULATIONS
 FROM A FLORIDA RESISTERED ENGINEER
 INDICATING THE REQUIRED DESIGN PRESSURES
 FOR THE ROOF OF THE STRUCTURE.
  
 6) SUBMIT SIGNED AND SEALED CALCULATIONS
 FROM A FLORIDA REGISTERED ENGINEER FOR
 INCREASED DESIGN PRESSURES.
  