Plan Review Notes
Plan Review Notes For Permit 05080092
Permit Number 05080092
Review Stop M
Sequence Number 1
Notes
Date Text
2005-09-12 00:00:00DENIED:BUILDING #2
 UNIT #101
 1.PLEASE CLARIFY ELEVATION & DISTANCE
 OF THE TERMINATION OF THE EXHAUST FROM
 THE GARAGE IN RELATION TO THE WINDOW
 FROM BEDROOM #2.PER 2001
 FBC(M)401.5.1, NOXIOUS EXHAUST SHALL BE
 TERMINATED A MINIMUN OF 10 FT FROM FRESH
 AIR INTAKES (I.E., DOORS OR WINDOWS).
 EXHAUST SHALL TERMINATE IN SUCH A MANNER
 AS NOT TO BE RECIRCULATED, 2001 FBC(M)
 501.3.
  
 2.RETURN AIR JUMPERS FROM THE MASTER
 BEDROOM ARE NOT SIZED PROPERLY.THE
 MASTER BEDROOM SHALL BE A MINIMUM OF 15"
 ROUND, 10" X 19" RECTANGLE OR EQUAL TO.
 RETURN AIR FROM A MASTER SUITE SHALL
 COMPLY WITH 2001 FBC(M)601.4 EXCEPTION
 #1 AND 3.
  
 3.PLAN SHEET M-1 INDICATES 4" O.A.
 DUCT CONNECTING TO THE RETURN AIR PLENUM
 BOX BELOW THE AHU.THE DETAIL ON PLAN
 SHEET M-2, THE AHU MOUNTING DETAIL DOES
 NOT REFLECT THE RETURN AIR PLENUM BOX.
 THE DETAIL INDICATES AN AUXILIARY DRAIN
 PAN IN THE RETURN AIR PLENUM?PLEASE
 CLARIFY.SHOULD THE AHU CLOSET BE THE
 RETURN AIR PLENUM, ALL COMPONENTS OF THE
 CLOSET SHALL COMPLY WITH 2001 FBC(M)
 602.2.1 & 2001 FBC CHAPTER 13 SUB
 CHAPTER 610.1.ABC.3.7.
  
 UNIT #102
 1.SEE COMMENT #1 FOR UNIT #101
 2.RETURN AIR JUMPER FROM THE MASTER
 SUITE SHALL BE A MINIMUM OF 14" ROUND,
 10" X 16" RECTANGLE OR EQUAL.
 3.SEE COMMENT #3 FOR UNIT #101.
  
 UNIT #103
 SEE COMMENTS 1 THROUGH 3 FOR UNIT #101.
 4.PLEASE CLARIFY THE ENERGY
 CALCULATIONS.BOTH UNIT # 101 & 103 ARE
 LOCATED ON THE GROUND LEVEL & END UNITS
 WITH THE SAME SQUARE FOOTAGE.UNIT #101
 INDICATES A 4 TON UNTI WERE UNIT 103 IS
 ONLY A 3.5 TON UNIT.
  
 UNIT #201
 PLEASE NOTE PLAN SHEET 6-A2 REFERENCES
 PLANS "4-A7GL, 4-A7GR-C & 4-A7GR", THIS
 SHOULD READ 6-A7GL,6A-GL-C (SHOULD BE
 'GR' NOT GL) & 6-A7GR".PLEASE
 CORRELATE PLANS.
 1.RETURN AIR FROM THE MASTER SUITE IS
 NOT SIZED IN ACCORDANCE WITH 2001 FBC(M)
 601.4 EXCEPTION #1 & 3.RETURN AIR
 JUMPER SHALL BE A MINIMUM OF 16" ROUND
 14" X 15" RECTANGLER OR EQUAL.
  
 2.RETURN AIR JUMPER NOT REQUIRED FROM
 THE LAUNDRY AREA.
  
 3.SEE COMMENT #3 FOR UNIT #101
  
 4.FAN SHUTDOWN WITH NOTIFICATION
 REQUIRED IN ACCORDANCE WITH 2001
 FBC(M)606.2.1 & 606.4.1.
  
 UNIT #202
 SEE ALL COMMENTS WITH THE EXCEPTION OF
 #4 FOR UNIT #201.
  
 UNIT #203
 1.RETURN AIR FROM THE MASTER SUITE
 SHALL BE A MINIMUM OF 18" ROUND OR EQUAL
 IN ACCORDANCE WITH 2001 FBC(M)601.4
 EXCEPTION #1 & 3.
  
 2.RETURN AIR NOT REQUIRED FROM THE
 LAUNDRY AREA.
  
 3.SEE COMMENT #3 FOR UNIT #101.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  