Date |
Text |
2006-02-16 00:00:00 | DENIED |
| (3RD REVIEW) |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE STRUCTURE IS LOCATED IN AN "AO" |
| FLOOD ZONE. AN ELEVATION CERTIFICATE |
| WILL BE REQUIRED. |
| |
| 3) ADDITIONAL PERMIT FEES ARE DUE. THE |
| CALCULATED VALUE OF THE STRUCTURE IS |
| $674,294.00. A WESTWARD EXPANSION FEE OF |
| $750.00 PER UNIT IS ALSO REQUIRED. |
| |
| 4)CONDOMINIUM V APARTMENTS.IF THE |
| DWELLING UNITS ARE TO BE SOLD AS |
| CONDOMINIUMS, A 'DECLARATION OF |
| CONDOMINIUM' SHALL BE SUBMITTED TO THE |
| STATE FOR APPROVAL, AND THEN RECORDED |
| WITH THE CLERK OF THE COUNTY COURT.A |
| RECORDED COPY SHALL BE SUBMITTED TO THE |
| CITY FOR RECORDS, ADDRESSING PURPOSES, |
| AND TO PALM BEACH COUNTY PROPERTY |
| APPRAISER'S OFFICE PRIOR TO C.O. |
| |
| 5)UNDER STRUCTURAL DESIGN CRITERIA ON |
| S5, THE CORRECT EDITIONS OF THE |
| REFERENCE STANDARDS ARE ACI 318-02 AND |
| ACI 530.1-02. PLEASE CORRECT. |
| |
| 6) SUBMIT SHOP DRAWINGS FOR THE |
| EXTERIOR GUARDRAILS. SPECIFY THE |
| ATTACHMENTS TO THE STRUCTURE. |
| |
| 7) PROVIDE SHOP DRAWINGS WITH |
| STRUCTURAL DETAILS FOR THE INTERIOR |
| GUARDRAIL AT THE SECOND FLOOR STAIRWELL |
| OPENING. |
| |
| 8) THE CONSTRUCTION TYPE IS SPECIFIED AS |
| TYPE V UNPROTECTED, UNSPRINKLERED. FBC |
| 2001 TABLE 600 REQUIRES EXTERIOR BEARING |
| WALLS TO BE FIRE RATED BASED ON DISTANCE |
| TO PROPERTY LINES OR ASSUMED PROPERTY |
| LINES. SPECIFY THE REQUIRED FIRE RATINGS |
| AND LOCATIONS OF THE RATED WALLS. |
| PROVIDE DETAILS AND SECTIONS OF WALLS |
| AND SPECIFY THE LISTED ASSEMBLIES FOR |
| THE FIRE RATED WALLS. |
| |
| 9) VERIFY THAT THE PERCENTAGE OF WALL |
| AREA ALLOWED AS OPENINGS BY TABLE 600 |
| BASED ON DISTANCE TO THE PROPERTY LINE |
| OR ASSUMED PROPERTY LINE IS NOT |
| EXCEEDED. |
| |
| 10) FBC 705 REQUIRES 3/4 HOUR OPENING |
| PROTECTIVES FOR FIRE RATED EXTERIOR |
| WALLS WITHIN 15' OF THE PROPERTY LINE. |
| SPECIFY HOW COMPLIANCE WILL BE |
| ACCOMPLISHED. |
| |
| 11) PLEASE REVISE NOTE 8 ON SHEET A9 |
| SECTION 1626 IS ONLY APPLICABLE TO THE |
| HVHZ. THE APPROPRIATE SECTION FOR AREAS |
| OUTSIDE THE HVHZ, WHICH ARE IN THE |
| WINDBOURNE DEBRIS REGION IS 1606.1.4. |
| THIS SECTION REQUIRES GLAZING TO BE |
| PROTECTED FROM WIND BOURNE DEBRIS. |
| |
| 12) SUBMIT PRODUCT APPROVALS FOR |
| STRUCTURAL WINDOW MULLIONS AND ROOF |
| COVERING MATERIAL. SPECIFY WHICH METHOD |
| OF ATTACHMENT WILL BE USED TO FASTEN THE |
| ROOF TILES. |
| |
| 13) ON SHEET A8GL THE 16' X 7' GARAGE |
| DOOR HAS THE WRONG ID TAG. |
| |
| 14) THE ROOF SHEATHING FASTENING NOTES |
| ON S4 AND S5 ARE INCORRECT. CITY |
| AMENDMENTS TO 2001 FBC TABLE 2306.1 |
| REQUIRE FASTENER SPACING TO BE 4"OC AT |
| THE EDGES AND 6"OC INTERMEDIATE IN ROOF |
| ZONE 3. PLEASE CORRECT. |
| |
| 15) SPECIFY THE TRUSS CONNECTORS THAT |
| WILL BE USED TO ATTACH THE TRUSSES |
| ABOVE THE GARAGES TO THE ONE HOUR FIRE |
| RATED TENANT SEPARATION WALLS. PROVIDE |
| DETAILS AND SECTION. SEE SHEET S-2. |
| |
| 16) SPECIFY THE TRUSS ANCHORS FOR THE |
| THREE PLY (A12) GIRDERS AT THE EXTERIOR |
| WALLS. TRUSS DRAWINGS SPECIFY 1795# |
| UPLIFT. SEE SHEET S-3. |
| |
| 17) THE OWNER/AGENT IS REQUIRED TO SIGN |
| THE ENERGY CALC. FORMS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |