Date Text
2005-12-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FHA-98 DESIGN MANUAL
  
 ***FROM PREVIOUS REVIEW***
  
 1. ALL FIRST FLOOR UNITS SHALL COMPLY
 WITH REQUIREMENTS 1 THRU 7 OF THE FAIR
 HOUSING ACT DESIGN MANUAL. PLEASE SUBMIT
 A DETAIL SHOWING COMPLIANCE WITH ALL
 REQUIREMENTS. INDICATE SPECIFICATION "A"
 OR "B" AS REQUIRED ON PAGE 7.34. THE
 CLEAR FLOOR SPACE FOR ALL USABLE
 FIXTURES SHALL BE APPLIED OR
 SUPERIMPOSED OVER THE FLOOR PLAN. FOR
 THE W/C SEE PAGE 7.43. - CLEAR FLOOR
 SPACE FOR THE W/C'S NOT SHOWN.
 4. SHTS P2 OF 2 ALL UNITS WATER HEATER
 DETAIL. P/T DISCHARGE LINE SHALL NOT
 HAVE ANY TRAPED SECTIONS. SECTION
 504.7.1. (SEE WATER HEATER NOTES).
 ****************NEW COMMENT*************
 1B. WATER HEATER PANS ON THE FIRST FLOOR
 ARE NOT REQUIRED. IF INSTALLED, THE
 ELEVATION ABOVE GRADE FOR THE PAN SHALL
 BE INDICATED SO AS TO INSURE THE PAN
 WILL DRAIN AS THE TERMINATION OF THE PAN
 DRAIN IS SHOWN AS 6" ABOVE GRADE.
 SECTIONS 104.2.1 & 504.8.
  
 REVIEW BY KEN STEVENS