Date |
Text |
2006-01-24 00:00:00 | DENIED |
| (2ND REVIEW) |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE STRUCTURE IS LOCATED IN AN "AO" |
| FLOOD ZONE. AN ELEVATION CERTIFICATE |
| WILL BE REQUIRED. |
| |
| 3) ADDITIONAL PERMIT FEES ARE DUE. THE |
| CALCULATED VALUE OF THE STRUCTURE IS |
| $674,294.00. A WESTWARD EXPANSION FEE OF |
| $550.00 PER UNIT IS ALSO REQUIRED. |
| |
| 4) THE SITE PLANS ARE REQUIRED WHICH |
| SPECIFY THE DISTANCE TO ASSUMED PROPERTY |
| LINES BETWEEN ADJACENT BUILDINGS LOCATED |
| ON THE SAME LOT. THIS IS REQUIRED IN |
| ORDER TO DETERMINE THE PERCENTAGE OF |
| WALL AREA THAT IS ALLOWED AS OPENINGS BY |
| FBC TABLE 600. |
| |
| 5) SHEETS A1 AND A9 REFERENCE THE 2004 |
| FBC AND THE STRUCTURAL PLANS ARE ON THE |
| 2001 FBC. THE PLANS WERE REVIEWED TO THE |
| 2001 FLORIDA BUILDING CODE. PLEASE |
| CORRECT THE CODE REFERENCE AND SECTIONS. |
| |
| 6) THE CONSTRUCTION TYPE SPECIFIED ON |
| SHEET 4-A1 IS FROM THE 2004 FBC. SPECIFY |
| THE CONSTRUCTION TYPE FROM THE 2001 FBC. |
| |
| 7)CONDOMINIUM V APARTMENTS.IF THE |
| DWELLING UNITS ARE TO BE SOLD AS |
| CONDOMINIUMS, A 'DECLARATION OF |
| CONDOMINIUM' SHALL BE SUBMITTED TO THE |
| STATE FOR APPROVAL, AND THEN RECORDED |
| WITH THE CLERK OF THE COUNTY COURT.A |
| RECORDED COPY SHALL BE SUBMITTED TO THE |
| CITY FOR RECORDS, ADDRESSING PURPOSES, |
| AND TO PALM BEACH COUNTY PROPERTY |
| APPRAISER'S OFFICE PRIOR TO C.O. |
| |
| 8) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 9)UNDER STRUCTURAL DESIGN CRITERIA ON |
| S5, THE CORRECT EDITIONS OF THE |
| REFERENCE STANDARDS ARE ACI 318-02 AND |
| ACI 530.1-02. PLEASE CORRECT. |
| |
| 10) SPECIFY THE METHOD OF TERMITE |
| PROTECTION THAT WILL BE USED AS REQUIRED |
| BY FBC 1816. |
| |
| 11)PRODUCT APPROVALS SUBMITTED |
| WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE |
| AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| BE SUBMITTED WITH A COVER SHEET THAT |
| LISTS THE PRODUCT IDENTITY NUMBER FROM |
| THE STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. PLEASE |
| SUBMIT THE FLORIDA PRODUCT APPROVAL |
| COVERSHEET WITH THE APPROPRIATE FL # AND |
| THE CORRESPONDING PRODUCT EVALUATION AND |
| INSTALLATION INSTRUCTIONS AS LISTED WITH |
| THE STATE ON THE PRODUCT APPROVAL |
| WEBSITE. |
| |
| 12) SPECIFY HOW IMPACT PROTECTION WILL |
| BE PROVIDED FOR THE GLAZED OPENINGS AS |
| REQUIRED BY FBC 1606.1.4. ITEM #13 OF |
| THE CITY OF WPB IMPLEMENTATION STANDARD |
| FOR HURRICANE MISSLE IMPACT PROTECTION |
| REQUIRES PRE-STORM PREPARATION PLANS TO |
| BE SUBMITTED FOR REVIEW IF USING STORM |
| SHUTTERS. A KEY PLAN, INSTALLATION |
| SCHEDULE AND PRODUCT APPROVALS ARE ALSO |
| REQUIRED. NOTE: STORM PANELS ARE NOT |
| ALLOWED ABOVE THE FIRST FLOOR FOR THIS |
| TYPE OF STRUCTURE AND OCCUPANCY. |
| |
| 13) SUBMIT THE EVALUATION REPORT AND |
| INSTALLATION INSTRUCTIONS FROM NATIONAL |
| ACCREDITATION ANS MANAGEMENT INSTITUTE |
| FOR THE THERMA-TRU DOORS WITH FL # 1170. |
| THE INFORMATION THAT WAS SUBMITTED TO |
| THE STATE FOR STATE PRODUCT APPROVAL IS |
| REQUIRED TO BE SUBMITTED WITH THE STATE |
| COVER SHEET. |
| |
| 14) SUBMIT PRODUCT APPROVAL FOR THE |
| SMALL (8' X 7') OVERHEAD GARAGE DOOR |
| WHICH IS LESS THAN THE MINIMUM SIZE |
| ALLOWED BY THE PRODUCT APPROVAL FOR THE |
| LARGE DOOR THAT WAS SUBMITTED. |
| |
| 15) SUBMIT PRODUCT APPROVALS FOR THE |
| TRUSS CONNECTORS. |
| |
| 16) THE ENGINEER IS REQUIRED TO SIGN HIS |
| NAME TO THE PLANS HE SEALS PER FAC |
| 61G15-23.002. PLEASE SUBMIT A NOTARIZED |
| LETTER SIGNED, SEALED AND DATED BY THE |
| ENGINEER ATTESTING HIS LEGAL SIGNATURE. |
| |
| 17) SUBMIT SIGNED AND SEALED TRUSS |
| DRAWINGS AND LAYOUTS THAT HAVE BEEN |
| REVIEWED AND APPROVED BY THE DESIGNER OF |
| RECORD FOR THE STRUCTURE. |
| |
| 18) SUBMIT SHOP DRAWINGS FOR THE |
| EXTERIOR GUARDRAILS. SPECIFY THE |
| ATTACHMENTS TO THE STRUCTURE. |
| |
| 19) PROVIDE SHOP DRAWINGS WITH |
| STRUCTURAL DETAILS FOR THE INTERIOR |
| GUARDRAIL AT THE SECOND FLOOR STAIRWELL |
| OPENING. |
| |
| 20) THE STRUCTURAL PLANS DO NOT SHOW THE |
| ELEVATOR RECESSES OR THE ELEVATOR |
| OPENINGS AT THE SECOND FLOOR. SUBMIT |
| STRUCTURAL DETAILS FOR THESE AREAS. |
| |
| 21) PROVIDE STRUCTURAL DETAILS FOR THE |
| INFILL FLOOR FRAMING AT THE ELEVATOR |
| RECESSES AND OPENINGS WHEN THE CLOSET |
| OPTION IS USED IN LEIU OF THE ELEVATOR. |
| SEE DETAILS 6 AND 7 ON A11. |
| |
| 22) ON SHEET A7GL THE DOOR TO THE |
| ELEVATOR HAS I.D. MARK #11 WHICH |
| ACCORDING TO THE DOOR SCHEDULE ON A9 IS |
| A 16' X 7' GARAGE DOOR. PLEASE CORRECT. |
| |
| 23) THE 16' X 7' GARAGE DOOR ON SHEETS |
| A8GR AND A8GL HAVE THE WRONG ID MARKS. |
| PLEASE CORRECT. |
| |
| 24) THE SCALE FOR SHEET A4 LISTED IN THE |
| DRAWING INDEX ON A1 IS INCORRECT. PLEASE |
| CORRECT. |
| |
| 25) THE WALL SECTION ON A13 SITES FBC |
| SECTIONS 2507.3 THRU 2507.5. THESE |
| SECTIONS DO NOT APPLY TO METAL LATH AND |
| THEY ARE REQUIREMENTS FOR THE HIGH |
| VELOCITY HURRICANE ZONE ONLY (DADE AND |
| BROWARD COUNTIES). PLEASE CORRECT. |
| |
| 26) THE 5' WIDE BI-PASS DOOR (#7 IN |
| SCHEDULE) SPECIFIED FOR HER WALK-IN |
| CLOSET DOES NOT COMPLY WITH FAIR HOUSING |
| REQUIREMENTS. CLOSET DOORS THAT REQUIRE |
| USERS TO PASS THROUGH THE DOORWAY TO |
| REACH THE CONTENTS ARE REQUIRED TO |
| PROVIDE AT LEAST A 31-5/8" CLEAR |
| OPENING. |
| |
| 27) NOTE 3 ON SHEET S5 UNDER PLYWOOD |
| ROOF DIAPHRAGM CONFLICTS WITH THE ROOF |
| NAILING SPECIFIED ON S4. CITY AMENDMENTS |
| TO FBC TABLE 2306.1 REQUIRE 8D RING |
| SHANK NAILS AT 4"OC AT EDGES AND 6"OC |
| INTERMEDIATE IN ZONE 3 FOR MEAN ROOF |
| HEIGHTS OF 25'-35'. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |