2005-09-10 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FHA-98 DESIGN MANUAL |
| |
| 1. ALL FIRST FLOOR UNITS SHALL COMPLY |
| WITH REQUIREMENTS 1 THRU 7 OF THE FAIR |
| HOUSING ACT DESIGN MANUAL. PLEASE SUBMIT |
| A DETAIL SHOWING COMPLIANCE WITH ALL |
| REQUIREMENTS. INDICATE SPECIFICATION "A" |
| OR "B" AS REQUIRED ON PAGE 7.34. THE |
| CLEAR FLOOR SPACE FOR ALL USABLE |
| FIXTURES SHALL BE APPLIED OR |
| SUPERIMPOSED OVER THE FLOOR PLAN. FOR |
| THE W/C SEE PAGE 7.43. |
| 2. SHTS P1 OF 2 FOR UNITS 101, 102, 201, |
| & 202, MAXIMUM 6 FT. FROM SHOWER TRAP TO |
| VENT PER TABLE 906.1. ON THE FLOOR PLAN |
| IT SCALES OUT TO APPROX. 8' TO 9'. |
| 3. SHTS P2 OF 2 FOR UNITS 101, 102, 201, |
| & 202, WATER RISER DIAGRAM. WATER HAMMER |
| ARRESTORS SHALL BE LOCATED NEAR THE |
| FIXTURE IN AN "EFFECTIVE RANGE" NOT IN |
| THE CEILING AS SOME ARE SHOWN. |
| PDI-WH 201 AND MANUF. INSTALLATION |
| INSTRUCTIONS. |
| 4. SHTS P2 OF 2 ALL UNITS WATER HEATER |
| DETAIL. P/T DISCHARGE LINE SHALL NOT |
| HAVE ANY TRAPED SECTIONS. SECTION |
| 504.7.1. (SEE WATER HEATER NOTES). |
| 5. SHTS P2 OF 2 ALL UNITS SANITARY RISER |
| DIAGRAM. THE WASH MACHINES DRAIN LINE |
| SHALL HAVE A STANDPIPE, SECTION 1002.1., |
| AND THE CLEANOUT SHALL BE LOCATED 4' |
| ABOVE THE FLOOR, SECTION 708.10 FOR |
| ACCESS. |
| |