Plan Review Notes
Plan Review Notes For Permit 05080090
Permit Number 05080090
Review Stop M
Sequence Number 1
Notes
Date Text
2005-09-20 00:00:00PLAN DENIED
 BLDG.#6
 APT.102,102,103
 1) PLEASE REFER TO SECTION 401.5.1
 INTAKE
 OPENING.FRESH AIR MUST BE 10 FT.FROM
 EXHAUST,DOORS,WINDOWS.
 2) PLEASE REFER TO SECTION 504.6 COLTHES
 DRYER DUCT.OVER 25 FT.
 3) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR.
 4) PLEASE REFER TO SECTION 301.14 FLOOD
 HAZARD.
 APT.201,203
 1) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR EXCPETION #3.
 TRANSFER DUCT IS NOT REQUIRED IN UTILITY
 ROOM.
 2) PLEASE REFER TO SECTION 606.2.1
 SUPPLY AIR SYSTEM.FOR FAN SHUTDOWN.
 3) PLEASE REFER TO SECTION 606.4.1
 SUPERVISION.
 4) PLEASE REFER TO SECTION 301.14 FLOOD
 HAZARD.
 APT.202
 1) PLEASE REFER TO SECTION 601.4
 BALANCED RETURN AIR EXCEPTION
  
 #3.TRANSFER DUCT IS NOT REQUIRED IN
 UITILY ROOM.
 2) PLEASE REFER TO SECTION 301.14 FLOOD
 HAZARD.
 3) PLEASE REFER TO SECTION 401.5.1
 INTAKE OPENING.
  
 PLAN REVIEW BY HAROLD MOSER 561-805-6732