Plan Review Notes For Permit 05080090 |
Permit Number |
05080090 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-20 00:00:00 | PLAN DENIED | | BLDG.#6 | | APT.102,102,103 | | 1) PLEASE REFER TO SECTION 401.5.1 | | INTAKE | | OPENING.FRESH AIR MUST BE 10 FT.FROM | | EXHAUST,DOORS,WINDOWS. | | 2) PLEASE REFER TO SECTION 504.6 COLTHES | | DRYER DUCT.OVER 25 FT. | | 3) PLEASE REFER TO SECTION 601.4 | | BALANCED RETURN AIR. | | 4) PLEASE REFER TO SECTION 301.14 FLOOD | | HAZARD. | | APT.201,203 | | 1) PLEASE REFER TO SECTION 601.4 | | BALANCED RETURN AIR EXCPETION #3. | | TRANSFER DUCT IS NOT REQUIRED IN UTILITY | | ROOM. | | 2) PLEASE REFER TO SECTION 606.2.1 | | SUPPLY AIR SYSTEM.FOR FAN SHUTDOWN. | | 3) PLEASE REFER TO SECTION 606.4.1 | | SUPERVISION. | | 4) PLEASE REFER TO SECTION 301.14 FLOOD | | HAZARD. | | APT.202 | | 1) PLEASE REFER TO SECTION 601.4 | | BALANCED RETURN AIR EXCEPTION | | | | #3.TRANSFER DUCT IS NOT REQUIRED IN | | UITILY ROOM. | | 2) PLEASE REFER TO SECTION 301.14 FLOOD | | HAZARD. | | 3) PLEASE REFER TO SECTION 401.5.1 | | INTAKE OPENING. | | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|