Plan Review Notes For Permit 05080090 |
Permit Number |
05080090 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-09-27 00:00:00 | ******DENIED****** | | | | 1) ADDRESS IS REQUIRED ON EACH BUILDING. | | IT SHALL BE A MINIMUM OF 3" AND | | CONTRASTING TO THE BACKGROUND. | | | | 2) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | REQUIREMENTS FOR ALL HANDRAILS AND | | GUARDS. | | | | 3) ARE THESE BUILDINGS FIRE SPRINKLERED? | | | | | | 4) FIRE HYDRANTS SHALL BE WET BEFORE, | | DURING AND AFTER CONSTRUCTION. | | | | 5) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | REQUIRED FOR EACH UNIT. | | | | 6) ELEVATORS SHALL COMPLY WITH A.S.M.E | | A-17.1. | | | | 7) PLEASE USE THE 2003 EDITION WHEN | | REFERENCING NFPA 101. SHT 4-A9. | | | | 8) SMOKE DETECTORS SHALL BE ARRANGED | | WHERE ACTIVATION OF ONE CAUSES ALL IN | | THE UNIT TO SOUND. | | | | 9) ALL CONSTRUCTION, ALTERATION AND | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | 10) STAIRS TO COMPLY WITH NFPA 101, | | SECTION 7.2.2. | | | | 11) SMOKE DETECTORS TO BE INSTALLED A | | MINIMUM OF 3' FROM HVAC DIFFUSERS. | | | | 12) PLEASE SEE SOME OF THE SMOKE | | DETECTORS NEAR #2 BEDROOMS APPEAR TO | | CLOSE TO THE BATHROOM. | | | | 13) HANDRAILS REQUIRED ON BOTH SIDES OF | | STAIRS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|