Plan Review Notes
Plan Review Notes For Permit 05080090
Permit Number 05080090
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-26 00:00:00***********UNSAT ************
  
 BLDG #6.
  
  
 1)NOTE: PLEASE CHECK AND VERIFY ALL SETS
 AND CORRECT SHEETS.
  
 2)NOTE: PLEASE SEE APPLICATION SHOWS
 THESE BEING SUBMITTED AS "TOWNHOUSES"??
 PLEASE SEE BUILDING REVIEW COMMENTS.
 THESE DO NOT SEEM TO BE CONSIDERED TRUE
 "TOWNHOUSES" AS DEFINED UNDER THE FBC.
 PLEASE SEE PALM BEACH COUNTY IMPACT FEE
 STAMPED INDICATES BUILDINGS AS 4 AND 6
 UNIT MULTI FAMILY DWELLINGS.
  
 PLEASE SEE THE FOLLOWING COMMENT FOR
 ELECTRICAL SERVICE.
  
 3)NOTE: PLEASE SEE DUE TO THESE NOT
 BEING CONSIDERED AS TOWNHOUSES WITH
 SEPARATE PROPERTY LINES, FEE SIMPLE ETC.
 ONLY ONE ELECTRICAL SERVICE WILL BE
 PERMITTED. PLEASE SEE GROUPING OF MAINS
 WILL BE REQUIRED FOR ALL FOUR UNITS IN
 THIS BLDG UNDER ONE SERVICE.
 PLEASE ADJUST SIZE OF SERVICE
 ACCORDINGLY. (SEC'S, GROUNDING,
 CONDUITS, ETC.
 230.2,230.70,230.72,240.4,310.16
  
 4)NOTE: PLEASE SEE MISSING AREAS FOR
 EGRESS LIGHTING. PLEASE SEE SOME AREAS
 WHERE AS "J-BOX" IS SHOWN, A LT FIXTURE
 OFSOME TYPE WILL BE REQUIRED. PLEASE
 SEE ENTRIES, TERRACE(1ST FLR) LIV RMS,
 KITCHENS ETC.
 PLEASE SEE 2-STORY UNITS, A 3-WAY OR
 4-WAY SWITCH WILL BE REQUIRED AT THE
 LANDINGS LOCATED IN BETWEEN FLRS.
 THIS IS ALSO REQUIRED FROM 210.70,LS 101
 5-8
  
 5)NOTE: PLEASE SEE MISSING SMOKE
 DETECTORS FOR AREAS LEADING TO FLR
 ABOVE. PLEASE SEE ENTRY FOYER'S FOR
 2-STORY UNITS. NFPA-72 8-1.4.1.6.2
 PLEASE ALSO SEE SD'S FOR MASTER BEDRM
 SHALL BE MOED "INTO" BEDRM AREA. PLEASE
 SEE ALL SD'S ARE TO BE INSTALLED WITHIN
 3' OF THE PEAK IN A SLOPE CEILING AND IN
 TRAY/ELEVATED CEILINGS WITHIN 12" OF MAX
 CEILING HEIGHT.
 NFPA-72 CHAPTER 2.
 PLEASE SEE SD'S ARE TO BE LOCATED NO
 CLOSER THAN 3' TO ANY KITCHEN OR BATH
 DOOR. AND 5' TO A RETURN AIR GRILL.
 NFAP-72 8-1.4.2
 PLEASE SEE SOME OF THESE HAVE BEEN
 REDLINED ON ONE SET OF PLANS.
  
 6)NOTE: PLEASE SEE SD'S ARE CIRCUITED TO
 KITCHEN/DINING LTS. THIS IS OK, HOWEVER
 PLEASE KNOW, THIS CIRCUIT WOULD BE ARC
 FAULT PROTECTED. PLEASE SEE THIS MEANS
 KITCHEN AND DINING RM LTS AS SHOWN WOULD
 BE INDICATED AS AFCI.
 PLEASE SEE SD'S MAY BE ON AN EXISITNG
 BEDRM ARC FAULT PROTECTED CIRCUIT.
 210.12, 2002 NEC.
  
 7)NOTE: PLEASE VERIFY OF GFI SHOWN IN
 KITCHEN IS "IN" THE PANTRY? PLEASE SEE
 KITCHENS WHEREPANTRY IS NOT SHOWN, AND
 A COUNTERSPACE IS ALSO NOT INDICATED??
  
 8)NOTE: PLEASE SEE MISSING GFI RECEPTS
 AND LTS FOR ELEVATOR PITAND EQUIPMENT
 SPACE. EACH SHALL CONTAIN DEDICATED
 CIRCUITS PER 620.23,620.24
  
 9)NOTE: PLEASE SEE PANEL "A" LOCATED IN
 UNIT, HOWEVER PANEL SCHEDULES INDICATES
 PANEL LOCATION IN GARAGE. PLEASE SEE
 201,202 ETC.
  
 PLEASE SEE MANY OF THE ABOVE ITEMS WERE
 REDLINED ON PLANS FOR AREAS OF NOTES.
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REVIEWERS, WHICH MAY AFFECT
 ELECTRICAL PLANS. (BLDG).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW