2005-09-13 00:00:00 | DENIED:BUILDING 1 (4 UNIT) |
| UNIT#101 |
| 1.PLEASE CLARIFY ELEVATION & DISTANCE |
| OF THE TERMINATION OF THE EXHAUST FROM |
| THE GARAGE IN RELATION TO THE WINDOW |
| FROM BEDROOM #2.PER 2001 FBC(M) |
| 401.5.1, NOXIOUS EXHAUST SHALL BE |
| TERMINATED A MINIMUM OF 10 FT FROM FRESH |
| AIR INTAKES (I.E. DOORS OR WINDOWS). |
| EXHAUST SHALL TERMINTE IN SUCH A MANNER |
| AS NOT TO BE RECIRCULATED, 2001 FBC(M) |
| 501.3. |
| |
| 2.RETURN AIR JUMPER FROM THE MASTER |
| BEDROOM ARE NOT SIZED PROPERLY. THE |
| MASTER BEDROOM SHALL BE A MINIMUM OF 15" |
| ROUND, 10" X 19", OR EQUAL TO. |
| |
| 3.PLAN SHEET M-1 INDICATES 4" O.A. |
| DUCT CONNECTING TO THE RETURN AIR PLENUM |
| BOX BELOW THE AHU.THE DETAIL ON PLAN |
| SHEET M-2, AHU MOUNTING DETAIL DOES NOT |
| REFLECT THE RETURN AIR PLENUM BOX.THE |
| DETAIL INDICATES AN AUXILIARY DRAIN PAN |
| IN THE RETURN AIR PLENUM?PLEASE |
| CLARIFY.SHOULD THE AHU CLOSET BE THE |
| RETURN AIR PLENUM, ALL COMPONENTS OF THE |
| CLOSET SHALL COMPLY WITH 2001 FBC(M) |
| 602.2.1 & 2001 FBC CHAPTER 13 SUB |
| CHAPTER 610.1.ABC.3.7. |
| |
| UNIT #102 |
| 1.SEE COMMENT #1 FOR UNIT 101 |
| 2.RETURN AIR FROM THE MASTER SUITE IS |
| BOARDER LINE, SHOULD BE INCREASED TO 10" |
| X 17" RECTANGLE OR EQUAL. |
| 3.SEE COMMENT #3 FOR UNIT 101. |
| |
| UNIT #201 |
| 1.RETURN AIR NOT REQUIRED FROM THE |
| LAUNDRY ROOM AREA. |
| 2.SEE COMMENT #3 FOR UNIT 101. |
| 3.FAN SHUTDOWN REQUIRED IN ACCORDANCE |
| WITH 2001 FBC(M)606.2.1 & 606.4.1. |
| |
| UNIT 202 |
| 1. RETURN AIR NOT REQUIRED FROM THE |
| LAUNDRY ROOM AREA. |
| 2.SEE COMMENT #3 FOR UNIT 101. |
| 3.FAN SHUTDOWN REQUIRED IN ACCORDANCE |
| WITH 2001 FBC(M)606.2.1 & 606.4.1. |
| |