Plan Review Notes
Plan Review Notes For Permit 05080080
Permit Number 05080080
Review Stop E
Sequence Number 8
Notes
Date Text
2006-11-28 13:04:05**** UNSAT ****
 REVISION #7
  
 ** PLEASE SEE THE FOLLOWING COMMENTS AS PLANS ARE
 COMING BACK WITH SOME REVISIONS; HOWEVER THERE ARE
 ITEMS NOW SHOWN AGAIN WHICH WERE COMMENTED ON AND
 CORRECTED FROM 2 REVIEWS AGO.
 PLEASE GO OVER PLANS CAREFULLY AND PLEASE CALL IF THERE
 ARE ANY QUESTIONS OR COMMENTS BASED ON THE FOLLOWING
 NOTES TYPED FOR THIS REVIEW.
 THIS IS REVISION NUMBER #7, UNLIKE THE PLANS WHICH
 INDICATE REVISION #5.
  
 1) NOTE: PLEASE KNOW ONE ITEM WHICH HAS BEEN GETTING
 REDLINED ON PLANS FROM THE PREVIOUS REVIEWS INCLUDING
 THE JOBSITE PLANS IS THE ADDRESS. PLEASE SEE THE
 ADDRESS IN OUR SYSTEM AND THE PERMITTED ADDRESS IS
 "6429", WHERE THE PLANS INDICATE "6425". THIS REVIEWER
 HAS BEEN CHANGING THIS BY HAND ON PLANS TO HELP IN
 GETTING THE REVISIONS DONE, HOWEVER AS PLANS ARE COMING
 BACK FOR OTHER COMMENTS PLEASE ADJUST THIS AT THIS
 TIME.
 PLEASE DO NOT KEEP SUBMITTING PLANS WITH THE OLD
 ADDRESS.
 FAC 61G1-16.004
  
 2) NOTE: PLEASE SEE THE POOL PANEL IS NOW MISSING FROM
 THE PLANS??? PLEASE SEE THE RISER STILL SHOWS THIS
 PANEL AND THERE IS A PANEL SCHEDULE SUBMITTED FOR THIS,
 YET PLANS WHICH PREVIOUSLY SHOWED THIS PANEL NO LONGER
 DOES?
 PLEASE SHOW.
 110.26, 240.24 ETC
 FBC ADMIN SECTION 106.1.2
  
 3) NOTE: PLEASE SEE PLANS NOW REPLACE THE DESIGNATION
 FOR WHAT USED TO BE THE SUB PANEL "B" TO NOW
 DESIGNATION FOR A SUB PANEL "E". PLEASE SEE THE RISER
 AND THE PANEL SCHEDULES DO NOT CORRELATE WITH THIS.
 IS THERE ANOTHER PANEL??
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE THE SUB PANEL B HAS NOW CHANGED THE
 FEEDERS ON THE RISER; HOWEVER THE PANEL SCHEDULE "A"
 STILL SHOWS #4'S??
 PLEASE CORRELATE THE SIZE OF THE FEEDERS AND VERIFY THE
 PANEL SIZE AS IT IS NOT KNOW THAT A 70A PANEL IS MADE?
 PLEASE KNOW IF THIS IS A 100A MLO, IT IS OK SHOWING A
 70A BREAKER IN PANEL ?A? FEED TO THIS PANEL.
 PLEASE CORRELATE AND SIZE CORRECTLY.
 408.4, 310.16, ETC
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE AHU WHICH HAS NOW CHANGED TO 8KW,
 YET STILL SHOWS 10KW? PLEASE CORRELATE AND ADJUST THE
 OVER CURRENT PROTECTION, CONDUCTOR SIZES ETC AS NEED.
 310.16, 424.3B, 240.4 ETC
  
 6) NOTE: PLEASE SEE ONE OF THE WATER HEATERS WHICH WERE
 SHOWN AS GAS ON THE PREVIOUS PLANS, HAVE NOW CHANGED TO
 ELECTRIC SHOWING A 4.5KW LOAD YET STILL SHOW FEEDING
 THIS WATER HEATER WITH A SINGLE POLE 20A CIRCUIT?
 PLEASE ADJUST AND CORRELATE. IF SOLAR THEN PLEASE
 SUBMIT THE SPEC/INFORMATION FOR THIS AS THIS IS THE
 FIRST PLAN WHICH INDICATES ANY SOLAR WATER HEATER.
 PLEASE SUBMIT THE MANUFACTURE SPECS/CUT SHEETS FOR THIS
 EQUIPMENT. 110.3, 90.7
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE SEE NOTES WHICH WERE ON PREVIOUS PLANS
 WHICH MENTIONED THE SMOKE DETECTORS BEING PART OF THE
 LOW VOLTAGE SECURITY, YET THESE NOTES HAVE BEEN REMOVED
 FROM BOTH SHEETS? PLEASE CLARIFY. IF THIS IS INDEED THE
 CASE PLEASE REPLACE NOTES, IF NOT PLEASE INDICATE AS
 "SA" FOR SMOKE ALARMS WHICH IS PART OF A 120V SYSTEM
 WHICH CONTAINS AN DETECTION AND ALARM IN THE SAME UNIT
 DEVICE.
 PLEASE SEE NFPA-72 DEFINITIONS FOR THIS.
  
 **** AS MENTIONED ON ALL PREVIOUS REVIEWS, IF THERE ARE
 ANY QUESTIONS, COMMENTS OR IF ANY OF THE COMMENTS ARE
 CONFUSING OR NOT UNDERSTOOD IN ANY WAY, PLEASE CALL.
 TO DATE THIS OFFICE HAS NOT RECEIVED ANY CALLS FROM THE
 ARCHITECT OF RECORD OVER THE LAST 6 OR SO REVIEWS WHICH
 HAVE BEEN DONE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]