2006-11-02 18:59:21 | ******** UNSAT ********* |
| |
| 1) NOTE: PLEASE SEE PLANS STILL INDICATE A PANEL "E" |
| AND RISER DOES NOT . PLEASE SEE COULD NOT LOCATE THE |
| POOL PANEL? |
| PLEASE CORRELATE AND SHOW. |
| PLEASE SEE RISER AND PANEL SHOWS SUB PANEL "B" BEING |
| FED FROM MAIN PANEL "A"WITH A 2P-70A AND #4, AND |
| PLEASE SEE RISER SHOWS #6'S. PLEASE SEE SUB PANEL "B" |
| IS SHOWN AS 70A MLO, HOWEVER THIS WOULD BE A 100A MLO |
| WITH THE 70A BREAKER FROM THE MAIN PANEL "B".? |
| |
| 2) NOTE: PLEASE SEE JACUZZI TUB WHICH HAS NOW REMOVED |
| CIRCUITING HOWEVER ALSO REMOVED GFI INDICATION FOR |
| PROTECTION. PLEASE SEE SYMBOL ON PLANS STILL INDICATES |
| A 220V JACUZZI PER THE SYMBOL LEGEND? |
| PLEASE CORRELATE IF 220V OR 120V AND INDICATE THE GFI |
| PROTECTION EITHER AT THE JACUZZI TUB UNIT OR THE PANEL |
| BREAKER. |
| |
| 3) NOTE: PLEASE SEE PANEL SCHEDULE(S) WHICH STILL |
| INDICATE 20A BREAKERS ON #14 CONDUCTORS? |
| 240.4, 310.16 |
| |
| 4) NOTE: PLEASE SEE SA'S SHOULD ALSO BE NOTED ON THE |
| ARC FAULT NOTE. PLEASE SEE NOTE SHOWS A "&" BUT THE |
| SA'S SD'S WAS REMOVED ? |
| 210.12 |
| |
| 5) NOTE: PLEASE SEE AHU#2 SHOWS 10KW AND 8KW FOR LOAD |
| ON THE SAME UNIT, PLEASE SEE 424.3B IN EITHER CASE AND |
| CORRELATE WITH THE LOAD CALCULATIONS. |
| |
| 6) NOTE: PLEASE SEE COUNTER SPACE RECEPT MISSING GFI |
| DESIGNATION. ()THIS COULD HAVE BEEN REDLINED) HOWEVER |
| PLEASE CORRECT AT THIS TIME. |
| 210.8A6 |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |