2006-10-13 18:48:57 | ****UNSAT **** |
| |
| 1) NOTE: PLEASE CORRELATE RISER , PLANS AND PANEL |
| SCHEDULE SUBMITTED. PLEASE SEE PANEL "E" WAS NOT SHOWN, |
| HOWEVER TWO 200A PANEL "A"'S ARE?? |
| FBC106.1.2 PLEASE KNOW AT THIS TIME SOME REVIEW OF |
| ITEMS CAN NOT BE VERIFIED FOR CODE COMPLIANCE. PLEASE |
| SEE THAT IS IS BEING "ASSUMED" THAT THE SECOND PANEL |
| "A" IS ACUTALLY PANEL "E", YET THIS PANEL LOAD DOES NOT |
| CORRELATE WITH LOAD ON PANEL "B" WHICH IS NOTED AS |
| FEEDING "E". PLEASE ALSO SEE THIS PANEL IS BEING SHOWN |
| AS 200A. |
| |
| 2) NOTE: PLEASE CORRELATE PANEL SCHEDULES WITH PLANS |
| AND CIRCUITING. PLEASE SEE THAT THERE ARE NUMEROUS |
| ITEMS WHICH DO NOT MATCH. PLEASE SEE MANY OF THESE |
| ITEMS ARE REDLINED ON PLANS HOWEVER A FEW ARE NOTED |
| BELOW TO SEE WHAT IS BEING MENTIONED. |
| PLEASE SEE JACUZZI/WHIRLPOOL TUB, SHOWS 220V AND ON TWO |
| PHASES AS 220V, YET SCHEDULE SHOWS 1-POLE? |
| PLEASE SEE B-24 WHICH IS SHOWN AS ICE MAKER, YET PLANS |
| ALSO SHOW THIS FEEDING FAN IN OFFICE. |
| PLEASE SEE B-29 WHICH IS SHOWN FEEDING FAN ALSO FEEDS |
| THE SAME JACUZZI CIRCUIT ABOVE. |
| PLEASE SEE A-15 WHICH FEEDS BATH(S) RECEPTS ALONG WITH |
| NUMEROUS RECEPTS IN LIVING ROOM AND GARAGE. (PLEASE SEE |
| 210.11C3,AS THE REQUIRED DEDICATED BATH(S) CIRCUIT(S) |
| ARE NOT PERMITTED TO FEED ANY OTHER AREAS. |
| PLEASE SEE SMOKE ALARMS BEING SHOWN ON MORE THAN ONE |
| CIRCUIT IS IS NOT POSSIBLE AS THESE ARE REQUIRED TO BE |
| WIRED "INLINE". IFON MORE THAN ONE CIRCUIT THIS WOULD |
| NOT WORK OR CREATE 220V TO A 120 UNIT. |
| PLEASE SEE B-30, SHOWS WINE UNIT ON PLANS, YET B-30 IS |
| PART OF THE CIRCUIT WHICH IS SHOWN FEEDING PANEL "E" |
| PLEASE SEE WH AND CENTRAL VAC BEING SHOWN ON THE SAME |
| CIRCUIT. A-18. |
| ETC. |
| |
| 3) NOTE: PLEASE SEE 20A BREAKER(S) ON CONDUCTORS ONLY |
| RATED FOR 15A'S PER 310.16. PLEASE SEE 240.4. |
| |
| |
| ** PLEASE KNOW, AS THERE ARE MANY ITEMS WHICH NEED |
| CORRELATING , PLEASE BE SURE TO CALL IF THERE ARE NAY |
| QUESTIONS. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |