Plan Review Notes
Plan Review Notes For Permit 05080080
Permit Number 05080080
Review Stop E
Sequence Number 5
Notes
Date Text
2006-10-13 18:48:57****UNSAT ****
  
 1) NOTE: PLEASE CORRELATE RISER , PLANS AND PANEL
 SCHEDULE SUBMITTED. PLEASE SEE PANEL "E" WAS NOT SHOWN,
 HOWEVER TWO 200A PANEL "A"'S ARE??
 FBC106.1.2 PLEASE KNOW AT THIS TIME SOME REVIEW OF
 ITEMS CAN NOT BE VERIFIED FOR CODE COMPLIANCE. PLEASE
 SEE THAT IS IS BEING "ASSUMED" THAT THE SECOND PANEL
 "A" IS ACUTALLY PANEL "E", YET THIS PANEL LOAD DOES NOT
 CORRELATE WITH LOAD ON PANEL "B" WHICH IS NOTED AS
 FEEDING "E". PLEASE ALSO SEE THIS PANEL IS BEING SHOWN
 AS 200A.
  
 2) NOTE: PLEASE CORRELATE PANEL SCHEDULES WITH PLANS
 AND CIRCUITING. PLEASE SEE THAT THERE ARE NUMEROUS
 ITEMS WHICH DO NOT MATCH. PLEASE SEE MANY OF THESE
 ITEMS ARE REDLINED ON PLANS HOWEVER A FEW ARE NOTED
 BELOW TO SEE WHAT IS BEING MENTIONED.
 PLEASE SEE JACUZZI/WHIRLPOOL TUB, SHOWS 220V AND ON TWO
 PHASES AS 220V, YET SCHEDULE SHOWS 1-POLE?
 PLEASE SEE B-24 WHICH IS SHOWN AS ICE MAKER, YET PLANS
 ALSO SHOW THIS FEEDING FAN IN OFFICE.
 PLEASE SEE B-29 WHICH IS SHOWN FEEDING FAN ALSO FEEDS
 THE SAME JACUZZI CIRCUIT ABOVE.
 PLEASE SEE A-15 WHICH FEEDS BATH(S) RECEPTS ALONG WITH
 NUMEROUS RECEPTS IN LIVING ROOM AND GARAGE. (PLEASE SEE
 210.11C3,AS THE REQUIRED DEDICATED BATH(S) CIRCUIT(S)
 ARE NOT PERMITTED TO FEED ANY OTHER AREAS.
 PLEASE SEE SMOKE ALARMS BEING SHOWN ON MORE THAN ONE
 CIRCUIT IS IS NOT POSSIBLE AS THESE ARE REQUIRED TO BE
 WIRED "INLINE". IFON MORE THAN ONE CIRCUIT THIS WOULD
 NOT WORK OR CREATE 220V TO A 120 UNIT.
 PLEASE SEE B-30, SHOWS WINE UNIT ON PLANS, YET B-30 IS
 PART OF THE CIRCUIT WHICH IS SHOWN FEEDING PANEL "E"
 PLEASE SEE WH AND CENTRAL VAC BEING SHOWN ON THE SAME
 CIRCUIT. A-18.
 ETC.
  
 3) NOTE: PLEASE SEE 20A BREAKER(S) ON CONDUCTORS ONLY
 RATED FOR 15A'S PER 310.16. PLEASE SEE 240.4.
  
  
 ** PLEASE KNOW, AS THERE ARE MANY ITEMS WHICH NEED
 CORRELATING , PLEASE BE SURE TO CALL IF THERE ARE NAY
 QUESTIONS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]