Plan Review Notes
Plan Review Notes For Permit 05080080
Permit Number 05080080
Review Stop E
Sequence Number 3
Notes
Date Text
2005-12-14 00:00:00**** UNSAT 3RD REVIEW ****
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW
 AND NEW NOTES DUE TO CHANGES IN PLANS.
  
  
 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS
 REVIEW WHICH REQUESTED TO SHOW THE
 POWER/OUTLET LOCAION ON PLANS FOR
 JACUZZI TUB. THIS WAS DONE , HOWEVER NOW
 THIS ISNOW SHOWING CIRCUITING ON PLANS
 FOR A 2-POLE UNIT(CIRCUITS 35 AND 37),
 PLEASE SEE PANEL SCHEDULE SHOWS THIS A A
 1-POLE 30A.
 PLEASE CORRELATE
  
 2)NOTE: PLEASE SEE NOTE #21 FROM
 PREVIOUS REVIEWS WHICH REQUESTED THE
 NEED TO CORRELATE THE RISER DIAGRAM,
 PANEL SCHEDULES ETC.
  
 A) PLEASE SEE RISER DIAGRAM STILL SHOWS
 TWO 200A DISCONNECTS WITH 200A FUSES,
 ALTHOUGH PANEL SCHEDULES ARE SUBMITTED
 INDICATING THESE AS 200A PANELS
 ("C"&"D") WITH NO INDICATION OF HAVING
 MCB'S???
  
 B)PLEASE ALSO SEE RISER INDICATES PANELS
 "A" AND "B" AS MAIN BREAKER PANELS, AND
 THESE PANEL SCHEDULES SHOWS MLO (MAIN
 LUG ONLY)??
  
 C)PLEASE NOW ALSO SEE PANEL SCHEDULES C
 AND D, INDICATE #2 FOR THE 200A FEED TO
 PANELS A AND B. PLEASE SEE 240.4, AND
 310.15B6/16 FOR THE MIN 2/0.
  
 3)NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS
 REVIEW WHICH STATED THE SD'S WERE ON
 MORE THAN ONE CIRCUIT A-19 AND B-13.
 PLEASE SEE CIRCUITING WAS REVISED ON 2ND
 FLR TO CIRCUIT A-24, HOWEVER FIRST FLR
 IS SHOWN AS A-13??
 ** PLEASE KNOW, THE SD'S ARE REQUIRED TO
 BE WIRED "INLINE" AND CAN NOT BE ON TWO
 SEPARATE CIRCUITS. THIS WOULD BE SENDING
 220V TO THE 120V SD"S.
 PLEASE ALSO SEE PLANS NOW HAVE A NOTE
 ADDED FOR SD'S WHICH REFERENCE THE OLD
 NFPA-72 8-1
 PLEASE SEE AS OF JAN 1ST, 2005, NFPA-72
 HAS CHANGED TO THE 2002 EDITION AND
 CODES FOR SD'S REFERENCE SHOULD BE
 11.5.1.1.
  
 4)NOTE: PLEASE SEE PREVIOUS NOTE #5
 WHICH MENTIONED CIRCUITING FOR MASTER
 BATH WAS IN ERROR. PLEASE SEE CIRCUITING
 FOR THIS MASTER BATH HAS NOW BEEN
 REVISED, HOWEVER PLEASE SEE PANEL
 SCHEDULE NOW MENTIONS THIS AS ARC FAULT
 AND ON THE SAME CIRCUIT AS THE MASTER
 BEDROOM.
 PLEASE SEE 210.52D,210.11C3
  
 5)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 THE DESIGN PROFESSIONAL AND REPEAT
 COMMENTS FOR CODE COMPLIANCE. IF PLANS
 COME BACK FOR REVIEW WITH ANY OF THE
 SAME CODE COMPLIANCE COMMENTS NOT
 ADDRESSED THIS OFFICE WILL HAVE NO
 CHOICE BUT TO ISSUE A 4X THE FEE FOR
 SAID REVIEW COMMENTS.
 THIS AMOUNT WOULD BE $12,600.00.
 ** TO THIS DATE NO ONE HAS CALLED TO GO
 OVER ANY COMMENTS IF THERE WERE ANY
 QUESTIONS, PLEASE KNOW IT IS STRONGLY
 SUGGESTED THAT A MEETING BE HELD TO GO
 OVER COMMENTS AND PLANS BEFORE
 RE-SUBMITTING PLANS FOR REVIEW AND ANY
 POSSIBLITY OF THE ABOVE BEING
 IMPLEMENTED.
  
 PLEASE DO NOT HESITATE IN CONTACTING
 MYSELF TO MEET AND/OR GO OVER THE ABOVE
 REFERENCED COMMENTS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  