2005-12-14 00:00:00 | **** UNSAT 3RD REVIEW **** |
| |
| ** PLEASE SEE NOTES FROM PREVIOUS REVIEW |
| AND NEW NOTES DUE TO CHANGES IN PLANS. |
| |
| |
| 1)NOTE: PLEASE SEE NOTE #1 FROM PREVIOUS |
| REVIEW WHICH REQUESTED TO SHOW THE |
| POWER/OUTLET LOCAION ON PLANS FOR |
| JACUZZI TUB. THIS WAS DONE , HOWEVER NOW |
| THIS ISNOW SHOWING CIRCUITING ON PLANS |
| FOR A 2-POLE UNIT(CIRCUITS 35 AND 37), |
| PLEASE SEE PANEL SCHEDULE SHOWS THIS A A |
| 1-POLE 30A. |
| PLEASE CORRELATE |
| |
| 2)NOTE: PLEASE SEE NOTE #21 FROM |
| PREVIOUS REVIEWS WHICH REQUESTED THE |
| NEED TO CORRELATE THE RISER DIAGRAM, |
| PANEL SCHEDULES ETC. |
| |
| A) PLEASE SEE RISER DIAGRAM STILL SHOWS |
| TWO 200A DISCONNECTS WITH 200A FUSES, |
| ALTHOUGH PANEL SCHEDULES ARE SUBMITTED |
| INDICATING THESE AS 200A PANELS |
| ("C"&"D") WITH NO INDICATION OF HAVING |
| MCB'S??? |
| |
| B)PLEASE ALSO SEE RISER INDICATES PANELS |
| "A" AND "B" AS MAIN BREAKER PANELS, AND |
| THESE PANEL SCHEDULES SHOWS MLO (MAIN |
| LUG ONLY)?? |
| |
| C)PLEASE NOW ALSO SEE PANEL SCHEDULES C |
| AND D, INDICATE #2 FOR THE 200A FEED TO |
| PANELS A AND B. PLEASE SEE 240.4, AND |
| 310.15B6/16 FOR THE MIN 2/0. |
| |
| 3)NOTE: PLEASE SEE NOTE #4 FROM PREVIOUS |
| REVIEW WHICH STATED THE SD'S WERE ON |
| MORE THAN ONE CIRCUIT A-19 AND B-13. |
| PLEASE SEE CIRCUITING WAS REVISED ON 2ND |
| FLR TO CIRCUIT A-24, HOWEVER FIRST FLR |
| IS SHOWN AS A-13?? |
| ** PLEASE KNOW, THE SD'S ARE REQUIRED TO |
| BE WIRED "INLINE" AND CAN NOT BE ON TWO |
| SEPARATE CIRCUITS. THIS WOULD BE SENDING |
| 220V TO THE 120V SD"S. |
| PLEASE ALSO SEE PLANS NOW HAVE A NOTE |
| ADDED FOR SD'S WHICH REFERENCE THE OLD |
| NFPA-72 8-1 |
| PLEASE SEE AS OF JAN 1ST, 2005, NFPA-72 |
| HAS CHANGED TO THE 2002 EDITION AND |
| CODES FOR SD'S REFERENCE SHOULD BE |
| 11.5.1.1. |
| |
| 4)NOTE: PLEASE SEE PREVIOUS NOTE #5 |
| WHICH MENTIONED CIRCUITING FOR MASTER |
| BATH WAS IN ERROR. PLEASE SEE CIRCUITING |
| FOR THIS MASTER BATH HAS NOW BEEN |
| REVISED, HOWEVER PLEASE SEE PANEL |
| SCHEDULE NOW MENTIONS THIS AS ARC FAULT |
| AND ON THE SAME CIRCUIT AS THE MASTER |
| BEDROOM. |
| PLEASE SEE 210.52D,210.11C3 |
| |
| 5)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) ATTACHED WITH RESPECT TO |
| THE DESIGN PROFESSIONAL AND REPEAT |
| COMMENTS FOR CODE COMPLIANCE. IF PLANS |
| COME BACK FOR REVIEW WITH ANY OF THE |
| SAME CODE COMPLIANCE COMMENTS NOT |
| ADDRESSED THIS OFFICE WILL HAVE NO |
| CHOICE BUT TO ISSUE A 4X THE FEE FOR |
| SAID REVIEW COMMENTS. |
| THIS AMOUNT WOULD BE $12,600.00. |
| ** TO THIS DATE NO ONE HAS CALLED TO GO |
| OVER ANY COMMENTS IF THERE WERE ANY |
| QUESTIONS, PLEASE KNOW IT IS STRONGLY |
| SUGGESTED THAT A MEETING BE HELD TO GO |
| OVER COMMENTS AND PLANS BEFORE |
| RE-SUBMITTING PLANS FOR REVIEW AND ANY |
| POSSIBLITY OF THE ABOVE BEING |
| IMPLEMENTED. |
| |
| PLEASE DO NOT HESITATE IN CONTACTING |
| MYSELF TO MEET AND/OR GO OVER THE ABOVE |
| REFERENCED COMMENTS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |