Plan Review Notes
Plan Review Notes For Permit 05080080
Permit Number 05080080
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-16 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE ZONING COMMENTS WHICH
 WILL HAVE A DIRECT AFFECT ON ELECTRICAL
 AND OTHER PLANS FOR HOUSE.
 PLEASE SEE BLDG REVIEW COMMENTS, SURVEY
 MUST CONTAIN AN ORIGINAL SIGNATURE FROM
 THE SURVEYOR OF RECORD. FS 472.025, FAC
 61G17-7.002
  
 2)NOTE: PLEASE SEE POOL/ POOL WIRING
 SHALL BE UNDER A SEPARATE PERMIT.
  
 3)NOTE: PLEASE CORRELATE ALL CIRCUITING
 SHOWN ON PLANS WITH THE PANEL SCHEDULES
 SUBMITTED. PLEASE SEE THERE ARE NUMEROUS
 CIRCUITS ON PLANS ETC WHICH DO NOT
 MATCH.
 PLEASE SEE COOK-TOP, TWO SETS OF
 DISHWASHER/ DISP,(NOT ON PLANS), SEE
 FLOOD LTS, WHIRLPOOL ETC.
 MMANY OF THESE HAVE BEEN REDLINED ON
 PLANS.
  
 4)NOTE: PLEASE SEE WHIRLPOOL WHICH IS
 SHOWN AS GEN LTS AND BEDRM CIRCUIT, IS
 REQUIRED TO HAVE GFI PROTECTION. PLEASE
 NOTE ON PANEL SCHEDULE, PLEASE SHOW
 LOCATION OF POWER OUTLET LOCATED AT WP
 TUB. PLEASE INDICATE REQUIRED ACCESS.
  
 5)NOTE: PLEASE SHOW LOCATIONS OF ALL
 SERVICE EQUIPMENT ON PLANS. PLEASE SEE
 METER ONLY SEEMS TO SHOW A DISC LOCATED
 NEXT TO IT.
 PLEASE SEE PANEL SCHEDULES ARE INDICATED
 AS "MAIN DISC'S" AND RISER SHOWS THESE
 AS MCB PANELS? PLEASE VERIFY IF THESE
 ARE "FEED- THRU" PANELS OR IS THERE OCP
 LOCATED IN EACH OF THESE PANELS FEEDING
 SUB-PANELS?
 215.5
  
 6)NOTE: PLEASE SEE NOTE ON PLANS
 MENTIONS, FPL TO USE 1/0 ALUM? PLEASE
 VERIFY THIS WITH A FPL SERVICE PLANNER
 AS SERVICE AND LOADS PROPOSED WOULD
 EXCEED FPL STANDARDS FOR 1/0'S AND A
 400A SERVICE.
 215.5
  
 7)NOTE: PLEASE SEE MAIN/PANEL "B" LOAD
 EXCEEDS, "FUTURE" PLANNING FOR ADDED
 LOADS. PLEASE SEE PANEL "B" WILL BE
 REQUIRED TO BE UPGRADED TO A MIN OF
 200A'S. PLEASE ADJUST.
 90.4,90.8
  
 8)NOTE: PLEASE SEE AN "EUIPMENT
 GROUNDING" CONDUCTOR IS ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
 PLEASE SEE AN EQUIPMENT GRND IS SHOWN
 FROM METER TO MAIN.
 250.6, 250.24 PLEASE REMOVE.
  
 9)NOTE: PLEASE SEE MIN GROUNDING
 ELECTRODE CONDUCTOR IS TO BE A 1/0 BASED
 ON 250.66, 310.15B6
 PLEASE ADJUST, #2 SHOWN.
  
 10)NOTE: PLEASE SEE 210.52C1 AND
 REDLINED PLANS FOR GFI RECEPTS REQUIRED
 ALONG KITCHEN COUNTERSPACE.
  
 11)NOTE: PLEASE SEE 210.8, ALL RECEPTS,
 LOCATED OUTSIDE, WITIN 6' OF ANY SINK,
 ETC SHALL BE GFI/GFI PROTECTED. PLEASE
 SEE , BAR AREAS, LAUNDRY RMS ETC.
 MANY OF THESE REDLINED ON PLANS.
  
 12)NOTE: PLEASE SEE ALL RECEPT SHOWN
 WITHIN 10' OF POOL ARE NOT PERMITTED AND
 MUST BE REMOVED. PLEASE SEE 680.22
 AMIN OF (1) GFI RECEPT IS REQUIRED
 WITH 20' OF A POOL BUT MUST BE ATLEAST
 10' FROM WATERS EDGE. PLEASE SEE THERE
 ARE RECEPTS SHOWN WITHIN THE 10' WHICH
 PROMOTES A "LIFE SAFETY" SITUATION.
 PLEASE ALSO SEE 680.22B4, FOR LIGHT
 FIXTURES NOT PERMITTED WITHIN 5'OF
 POOL'S WATER EDGE. PLEASE SEE ANY LTS
 WITHIN 5-10' , MUST BE ATLEAST 5' ABOVE
 MAX WATER LINE AND MUST ALSO BE GFI
 PROTECTED. PLEASE SEE SOME FIXTURES MAY
 NOT BE INSTALLED AT ALL , AS THEY ARE
 LESS THAN 5' FROMWATER'S EDGE.
 THIS IS A "LIFE SAFETY" SITUATION.
  
 13)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS PER 2', 6', AND 12' RULE.
 PLEASE SEE MANY OF THESE AREAS ARE
 REDLINED ON PLANS AT LOCATIONS BUT NOT
 ALL.
 PLEASE SEE ATRIUM,OFFICE, FAMILY RM,
 LIVING RM ETC.
  
 14)NOTE: PLEASE SEE RECEPT SHOWN FOR
 OUTSIDE WINE CU, TO BE GFI 210.8
  
 15)NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARNECE REQUIRED FOR A/C CU
 DISCONNECTS.440.11
  
 16)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4,
 NFPA-72 8-1.4.1.6.2
 PLEASE NOTE INSTALLATION PER NFPA-72
 8-1.4.2 ON PLANS.
 PLEASE SEE MANY OF THE SMOKE DETECTORS
 ARE REDLINED ON PLANS. PLEASE SEE OFFICE
 WILL BE REQUIRED TO HAVE A SD.
  
 17)NOTE: PLEASE SEE A "NOTE" ON PLANS
 E-1, MENTIONS ARC FAULT PROTECTION FOR
 RECEPTS ONLY.
 PLEASE SEE 2002 NEC 210.12,WHICH
 REQUIRES ARC FAULT PROTECTION FOR ALL
 "OUTLETS". PLEASE SEE E-2 SEEMS TO NOTE
 THIS.
  
 18)NOTE: PLEASE SEE PLANS "GEN NOTES"
 #1, REFERENCE "PALM BEACH COUNTY",
 PLEASE SEE, SINCE THIS PROJECT IS
 LOCATED IN THE CITY LIMITS, PLANS WOULD
 BE REQUIRED TO REFERENCE CITY OF WEST
 PALM BEACH.
  
 19)NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATION(S) ON ELECTRICAL PLANS.
 215.5
  
 20)NOTE: PLEASE SHOW ALL "CONTINUOUS
 LOADS" (3 OR MORE HRS)ARE SHOWN AT 125%
 ON LOAD CALCULATIONS.
 215.3,230.42 ETC.
  
 21)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
 ** PLEASE SEE THERE ARE OVER 110
 RECESSED LT FIXTURES SHOWN.
 PLEAS ADJUST LOAD CALCULATIONS.
  
 22)NOTE: PLEASE SEE "POOL EQUIPMENT" MAY
 NOT BE LOCATED AT LOCATION SHOWN AS
 BEING "UNDER" WOOD DECK WITHIN THE POOL
 AREA OF 5'.
 680.22 ETC. PLEASE ALSO SEE POSSIBLE
 COMMENTS FORM OTHER TRADES.
  
 23)NOTE: PLEASE SEE NUMEROUS BATH
 RECEPTS CIRCUITS WHICH ARE SHOWN AS #14,
 15A CIRCUITS. PLEASE SEE 210.52,210.11C3
 WHICH REQUIRES DEDICATED BATH(S)
 CIRCUIT(S). PLEASE SEE THESE ARE
 REQUIRED TO BE 20A AND #12, PLEASE
 ADJUST CIRCUITING AND PANEL SCHEDULES.
  
 24)NOTE: PLEASE VERIFY OCP SHOWN FOR
 AHU#3, THIS IS SHOWN AS A 7.5KW UNIT,
 HOWEVER LOAD CALCULATIONS AND OCP SHOW
 THIS AS A 10KW UNIT. PLEASE CORRELATE
 AND ADJUST.
  
 25)NOTE: PLEASE VERIFY GARAGE DOOR
 OPENERS AND LOAD (HP RATING) FOR EACH.
 PLEASE SEE 430.53 AND POSSIBLE A MIN OF
 TWO GDO CIRCUITS.
  
 26)NOTE: PLEASE SEE PLANS AND VERIFY ALL
 PHONE AND CATV LOCATIONS WHICH ARE GOING
 TO BE INCLUDED UNDER THIS PERMIT.
 (MASTER BEDRM PHONE?)
 THIS IS ONLY A NOTE.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE BE SURE ONE SET OF ALL OLD/VOIDED
 SHEETS REMOVED ARE SUBMITTED BACK FOR
 REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved