Date |
Text |
2005-08-16 00:00:00 | ************* UNSAT ****************** |
| |
| 1)NOTE: PLEASE SEE ZONING COMMENTS WHICH |
| WILL HAVE A DIRECT AFFECT ON ELECTRICAL |
| AND OTHER PLANS FOR HOUSE. |
| PLEASE SEE BLDG REVIEW COMMENTS, SURVEY |
| MUST CONTAIN AN ORIGINAL SIGNATURE FROM |
| THE SURVEYOR OF RECORD. FS 472.025, FAC |
| 61G17-7.002 |
| |
| 2)NOTE: PLEASE SEE POOL/ POOL WIRING |
| SHALL BE UNDER A SEPARATE PERMIT. |
| |
| 3)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| SHOWN ON PLANS WITH THE PANEL SCHEDULES |
| SUBMITTED. PLEASE SEE THERE ARE NUMEROUS |
| CIRCUITS ON PLANS ETC WHICH DO NOT |
| MATCH. |
| PLEASE SEE COOK-TOP, TWO SETS OF |
| DISHWASHER/ DISP,(NOT ON PLANS), SEE |
| FLOOD LTS, WHIRLPOOL ETC. |
| MMANY OF THESE HAVE BEEN REDLINED ON |
| PLANS. |
| |
| 4)NOTE: PLEASE SEE WHIRLPOOL WHICH IS |
| SHOWN AS GEN LTS AND BEDRM CIRCUIT, IS |
| REQUIRED TO HAVE GFI PROTECTION. PLEASE |
| NOTE ON PANEL SCHEDULE, PLEASE SHOW |
| LOCATION OF POWER OUTLET LOCATED AT WP |
| TUB. PLEASE INDICATE REQUIRED ACCESS. |
| |
| 5)NOTE: PLEASE SHOW LOCATIONS OF ALL |
| SERVICE EQUIPMENT ON PLANS. PLEASE SEE |
| METER ONLY SEEMS TO SHOW A DISC LOCATED |
| NEXT TO IT. |
| PLEASE SEE PANEL SCHEDULES ARE INDICATED |
| AS "MAIN DISC'S" AND RISER SHOWS THESE |
| AS MCB PANELS? PLEASE VERIFY IF THESE |
| ARE "FEED- THRU" PANELS OR IS THERE OCP |
| LOCATED IN EACH OF THESE PANELS FEEDING |
| SUB-PANELS? |
| 215.5 |
| |
| 6)NOTE: PLEASE SEE NOTE ON PLANS |
| MENTIONS, FPL TO USE 1/0 ALUM? PLEASE |
| VERIFY THIS WITH A FPL SERVICE PLANNER |
| AS SERVICE AND LOADS PROPOSED WOULD |
| EXCEED FPL STANDARDS FOR 1/0'S AND A |
| 400A SERVICE. |
| 215.5 |
| |
| 7)NOTE: PLEASE SEE MAIN/PANEL "B" LOAD |
| EXCEEDS, "FUTURE" PLANNING FOR ADDED |
| LOADS. PLEASE SEE PANEL "B" WILL BE |
| REQUIRED TO BE UPGRADED TO A MIN OF |
| 200A'S. PLEASE ADJUST. |
| 90.4,90.8 |
| |
| 8)NOTE: PLEASE SEE AN "EUIPMENT |
| GROUNDING" CONDUCTOR IS ONLY INSTALLED |
| AFTER THE FIRST MEANS OF DISCONNECT. |
| PLEASE SEE AN EQUIPMENT GRND IS SHOWN |
| FROM METER TO MAIN. |
| 250.6, 250.24 PLEASE REMOVE. |
| |
| 9)NOTE: PLEASE SEE MIN GROUNDING |
| ELECTRODE CONDUCTOR IS TO BE A 1/0 BASED |
| ON 250.66, 310.15B6 |
| PLEASE ADJUST, #2 SHOWN. |
| |
| 10)NOTE: PLEASE SEE 210.52C1 AND |
| REDLINED PLANS FOR GFI RECEPTS REQUIRED |
| ALONG KITCHEN COUNTERSPACE. |
| |
| 11)NOTE: PLEASE SEE 210.8, ALL RECEPTS, |
| LOCATED OUTSIDE, WITIN 6' OF ANY SINK, |
| ETC SHALL BE GFI/GFI PROTECTED. PLEASE |
| SEE , BAR AREAS, LAUNDRY RMS ETC. |
| MANY OF THESE REDLINED ON PLANS. |
| |
| 12)NOTE: PLEASE SEE ALL RECEPT SHOWN |
| WITHIN 10' OF POOL ARE NOT PERMITTED AND |
| MUST BE REMOVED. PLEASE SEE 680.22 |
| AMIN OF (1) GFI RECEPT IS REQUIRED |
| WITH 20' OF A POOL BUT MUST BE ATLEAST |
| 10' FROM WATERS EDGE. PLEASE SEE THERE |
| ARE RECEPTS SHOWN WITHIN THE 10' WHICH |
| PROMOTES A "LIFE SAFETY" SITUATION. |
| PLEASE ALSO SEE 680.22B4, FOR LIGHT |
| FIXTURES NOT PERMITTED WITHIN 5'OF |
| POOL'S WATER EDGE. PLEASE SEE ANY LTS |
| WITHIN 5-10' , MUST BE ATLEAST 5' ABOVE |
| MAX WATER LINE AND MUST ALSO BE GFI |
| PROTECTED. PLEASE SEE SOME FIXTURES MAY |
| NOT BE INSTALLED AT ALL , AS THEY ARE |
| LESS THAN 5' FROMWATER'S EDGE. |
| THIS IS A "LIFE SAFETY" SITUATION. |
| |
| 13)NOTE: PLEASE SEE 210.52 FOR MISSING |
| RECEPTS PER 2', 6', AND 12' RULE. |
| PLEASE SEE MANY OF THESE AREAS ARE |
| REDLINED ON PLANS AT LOCATIONS BUT NOT |
| ALL. |
| PLEASE SEE ATRIUM,OFFICE, FAMILY RM, |
| LIVING RM ETC. |
| |
| 14)NOTE: PLEASE SEE RECEPT SHOWN FOR |
| OUTSIDE WINE CU, TO BE GFI 210.8 |
| |
| 15)NOTE: PLEASE SEE 110.26 FOR MIN |
| CLEARNECE REQUIRED FOR A/C CU |
| DISCONNECTS.440.11 |
| |
| 16)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4, |
| NFPA-72 8-1.4.1.6.2 |
| PLEASE NOTE INSTALLATION PER NFPA-72 |
| 8-1.4.2 ON PLANS. |
| PLEASE SEE MANY OF THE SMOKE DETECTORS |
| ARE REDLINED ON PLANS. PLEASE SEE OFFICE |
| WILL BE REQUIRED TO HAVE A SD. |
| |
| 17)NOTE: PLEASE SEE A "NOTE" ON PLANS |
| E-1, MENTIONS ARC FAULT PROTECTION FOR |
| RECEPTS ONLY. |
| PLEASE SEE 2002 NEC 210.12,WHICH |
| REQUIRES ARC FAULT PROTECTION FOR ALL |
| "OUTLETS". PLEASE SEE E-2 SEEMS TO NOTE |
| THIS. |
| |
| 18)NOTE: PLEASE SEE PLANS "GEN NOTES" |
| #1, REFERENCE "PALM BEACH COUNTY", |
| PLEASE SEE, SINCE THIS PROJECT IS |
| LOCATED IN THE CITY LIMITS, PLANS WOULD |
| BE REQUIRED TO REFERENCE CITY OF WEST |
| PALM BEACH. |
| |
| 19)NOTE: PLEASE PROVIDE ALL ROOM AND |
| AREA DESIGNATION(S) ON ELECTRICAL PLANS. |
| 215.5 |
| |
| 20)NOTE: PLEASE SHOW ALL "CONTINUOUS |
| LOADS" (3 OR MORE HRS)ARE SHOWN AT 125% |
| ON LOAD CALCULATIONS. |
| 215.3,230.42 ETC. |
| |
| 21)NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| ** PLEASE SEE THERE ARE OVER 110 |
| RECESSED LT FIXTURES SHOWN. |
| PLEAS ADJUST LOAD CALCULATIONS. |
| |
| 22)NOTE: PLEASE SEE "POOL EQUIPMENT" MAY |
| NOT BE LOCATED AT LOCATION SHOWN AS |
| BEING "UNDER" WOOD DECK WITHIN THE POOL |
| AREA OF 5'. |
| 680.22 ETC. PLEASE ALSO SEE POSSIBLE |
| COMMENTS FORM OTHER TRADES. |
| |
| 23)NOTE: PLEASE SEE NUMEROUS BATH |
| RECEPTS CIRCUITS WHICH ARE SHOWN AS #14, |
| 15A CIRCUITS. PLEASE SEE 210.52,210.11C3 |
| WHICH REQUIRES DEDICATED BATH(S) |
| CIRCUIT(S). PLEASE SEE THESE ARE |
| REQUIRED TO BE 20A AND #12, PLEASE |
| ADJUST CIRCUITING AND PANEL SCHEDULES. |
| |
| 24)NOTE: PLEASE VERIFY OCP SHOWN FOR |
| AHU#3, THIS IS SHOWN AS A 7.5KW UNIT, |
| HOWEVER LOAD CALCULATIONS AND OCP SHOW |
| THIS AS A 10KW UNIT. PLEASE CORRELATE |
| AND ADJUST. |
| |
| 25)NOTE: PLEASE VERIFY GARAGE DOOR |
| OPENERS AND LOAD (HP RATING) FOR EACH. |
| PLEASE SEE 430.53 AND POSSIBLE A MIN OF |
| TWO GDO CIRCUITS. |
| |
| 26)NOTE: PLEASE SEE PLANS AND VERIFY ALL |
| PHONE AND CATV LOCATIONS WHICH ARE GOING |
| TO BE INCLUDED UNDER THIS PERMIT. |
| (MASTER BEDRM PHONE?) |
| THIS IS ONLY A NOTE. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| PLEASE BE SURE ONE SET OF ALL OLD/VOIDED |
| SHEETS REMOVED ARE SUBMITTED BACK FOR |
| REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
| |