Plan Review Notes
Plan Review Notes For Permit 05080074
Permit Number 05080074
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-10 00:00:00PAUL SCHMITZ, PLUMBING & GAS PLANS
 EXAMINERDENIED
 561-805-6692
 [email protected]
  
 REVIEW FBC 2001 CH 11
 FLORIDA ACCESIBILITY CODE.
  
 (1) ?11-4.21 SHOWER STALLS.
 ?11-4.21.1 GENERAL. ACCESSIBLE SHOWER
 STALLS SHALL COMPLY WITH ?11-4.21.
 ?11-4.21.2 SIZE AND CLEARANCES. EXCEPT
 AS SPECIFIED IN ?11-9.1.2, SHOWER
 STALL SIZE AND CLEAR FLOOR SPACE SHALL
 COMPLY WITH FIGURE 11-35(A) OR
 FIGURE 11-35(B).THE SHOWER STALL IN
 FIGURE 11-35(A) SHALL BE 36
 INCHES BY 36 INCHES (915 MM BY 915
 MM).SHOWER STALLS REQUIRED BY
 ?11-9.1.2 SHALL COMPLY WITH FIGURE
 11-57(A) OR FIGURE 11-57(B).THE
 SHOWER STALL IN FIGURE 11-35(B) WILL
 FIT INTO THE SPACE REQUIRED FOR A
 BATHTUB.
 ?11-4.21.4 GRAB BARS. GRAB BARS
 COMPLYING WITH ?11-4.26 SHALL BE
 PROVIDEDAS SHOWN IN FIGURE 11-37.
 ?11-4.21.5 CONTROLS. FAUCETS AND OTHER
 CONTROLS COMPLYING WITH ?11-4.27.4
 SHALL BE LOCATED AS SHOWN IN FIGURE
 11-37.IN SHOWER STALLS 36 INCHES
 BY 36 INCHES (915 MM BY 915 MM), ALL
 CONTROLS, FAUCETS, AND THE SHOWER
 UNIT SHALL BE MOUNTED ON THE SIDE WALL
 OPPOSITE THE SEAT.
 ?11-4.21.6 SHOWER UNIT. A SHOWER SPRAY
 UNIT WITH A HOSE AT LEAST 60
 INCHES (1525 MM) LONG THAT CAN BE USED
 BOTH AS A FIXED SHOWER HEAD AND AS
 A HAND-HELD SHOWER SHALL BE PROVIDED.
  
 (2)?11-4.18 URINALS.
 ?11-4.18.1 GENERAL. ACCESSIBLE URINALS
 SHALL COMPLY WITH ?11-4.18.
 ?11-4.18.2 HEIGHT. URINALS SHALL BE
 STALL-TYPE OR WALL-HUNG WITH AN
 ELONGATED RIM AT A MAXIMUM OF 17
 INCHES (430 MM) ABOVE THE FINISH FLOOR.
 ?11-4.18.3 CLEAR FLOOR SPACE. A CLEAR
 FLOOR SPACE 30 INCHES BY 48 INCHES
 (760 MM BY 1220 MM) SHALL BE PROVIDED
 IN FRONT OF URINALS TO ALLOW FORWARD
 APPROACH.THIS CLEAR SPACE SHALL
 ADJOIN OR OVERLAP AN ACCESSIBLE ROUTE
 AND SHALL COMPLY WITH ?11-4.2.4.
 URINAL SHIELDS THAT DO NOT EXTEND BEYOND
 THE FRONT EDGE OF THE URINAL RIM MAY BE
 PROVIDED WITH 29 INCHES (735 MM)
 CLEARANCE BETWEEN THEM.
 ?11-4.18.4 FLUSH CONTROLS. FLUSH
 CONTROLS SHALL BE HAND OPERATED OR
 AUTOMATIC, AND SHALL COMPLY WITH
 ?11-4.27.4, AND SHALL BE MOUNTED NO MORE
 THAN 44 INCHES (1120 MM) ABOVE THE
 FINISH FLOOR.
  
 (3) 11-4.17 TOILET STALLS.
 ?11-4.17.1 LOCATION. ACCESSIBLE TOILET
 STALLS SHALL BE ON AN ACCESSIBLE
 ROUTE AND SHALL MEET THE REQUIREMENTS
 OF ?11-4.17.
 ?11-4.17.2 WATER CLOSETS.
 WATER CLOSETS IN ACCESSIBLE STALLS SHALL
 COMPLY WITH ?11-4.16.
 ?11-4.17.3 SIZE AND ARRANGEMENT. THE
 SIZE AND ARRANGEMENT OF THE
 STANDARD TOILET STALL SHALL COMPLY
 WITH FIGURE 11-30(A), STANDARD STALL.
 STANDARD TOILET STALLS WITH A MINIMUM
 DEPTH OF 56 INCHES (1420 MM) (SEE
 FIGURE 11-30(A)) SHALL HAVE
 WALL-MOUNTED WATER CLOSETS.IF THE
 DEPTH OF A
 STANDARD TOILET STALL IS INCREASED AT
 LEAST 3 INCHES (75 MM), THEN A
 FLOOR-MOUNTED WATER CLOSET MAY BE
 USED.ARRANGEMENTS SHOWN FOR STANDARD
 TOILET STALLS MAY BE REVERSED TO ALLOW
 EITHER A LEFT- OR RIGHT-HAND
 APPROACH.ADDITIONAL STALLS SHALL BE
 PROVIDED IN CONFORMANCE WITH
 ?11-4.22.4
 ?11-4.17.4 TOE CLEARANCES. IN STANDARD
 STALLS, THE FRONT PARTITION AND
 AT LEAST ONE SIDE PARTITION SHALL
 PROVIDE A TOE CLEARANCE OF AT LEAST 9
 INCHES (230 MM) ABOVE THE FLOOR.IF
 THE DEPTH OF THE STALL IS GREATER
 THAN 60 INCHES (1525 MM), THEN THE TOE
 CLEARANCE IS NOT REQUIRED.
 ?11-4.17.5 DOORS.
 TOILET STALL DOORS, INCLUDING DOOR
 HARDWARE, SHALL COMPLY WITH ?11-4.13.
 THE DOORS SHALL BE SELF CLOSING.IF
 TOILET STALL APPROACH IS FROM LATCH
 SIDE OF THE STALL DOOR, CLEARANCE
 BETWEEN THE DOOR SIDE OF THE STALL AND
 ANY OBSTRUCTION MAY BE REDUCED TO A
 MINIMUM OF 42 INCHES (1065 MM) (SEE
 FIGURE 11-30).DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE OF ANY
 FIXTURE.
 ?11-4.17.6 GRAB BARS. GRAB BARS
 COMPLYING WITH THE LENGTH AND
 POSITIONING SHOWN IN FIGURE 11-30(A),
 FIGURE 11-30(B), FIGURE 11-30(C),
 AND FIGURE 11-30(D) SHALL BE PROVIDED.
 GRAB BARS MAY BE MOUNTED WITH
 ANY DESIRED METHOD AS LONG AS THEY
 HAVE A GRIPPING SURFACE AT THE
 LOCATIONS SHOWN AND DO NOT OBSTRUCT
 THE REQUIRED CLEAR FLOOR AREA.GRAB
 BARS SHALL COMPLY WITH ?11-4.26.
  
 (4) 11-4.22 TOILET ROOMS.
 ?11-4.22.1 MINIMUM NUMBER. TOILET
 FACILITIES REQUIRED TO BE ACCESSIBLE
 BY ?11-4.1 SHALL COMPLY WITH ?11-4.22.
 ACCESSIBLE TOILET ROOMS SHALL BE
 ON AN ACCESSIBLE ROUTE.
 ?11-4.22.2 DOORS.
 ?11-4.22.2(1) ALL DOORS TO
 ACCESSIBLE TOILET ROOMS SHALL COMPLY
 WITH
 ?11-4.13.DOORS SHALL NOT SWING
 INTO THE CLEAR FLOOR SPACE REQUIRED
 FOR ANY FIXTURE.
 ?11-4.22.3 CLEAR FLOOR SPACE. THE
 ACCESSIBLE FIXTURES AND CONTROLS
 REQUIRED IN ?11-4.22.4, ?11-4.22.5,
 ?11-4.22.6, AND ?11-4.22.7 SHALL BE
 ON AN ACCESSIBLE ROUTE.AN
 UNOBSTRUCTED TURNING SPACE COMPLYING
 WITH 11-4.2.3 SHALL BE PROVIDED WITHIN
 AN ACCESSIBLE TOILET ROOM.
 THE CLEAR FLOORSPACE AT FIXTURES AND
 CONTROLS, THE ACCESSIBLE ROUTE, AND THE
 TURNING
 SPACE MAY OVERLAP.
  
 END OF COMMENTS
  
  
  
  
  