Plan Review Notes
Plan Review Notes For Permit 05080065
Permit Number 05080065
Review Stop M
Sequence Number 2
Notes
Date Text
2005-11-21 00:00:00PROVISO:
 SITE PLAN DOES NOT INDICATE DISTANCES
 FROM OPENING INTO THE HOME (DOORS,
 WINDOWS, OR FRESH AIR INTAKES).PER
 2001 FBC(M)804.3.4 #3, VENT SYSTEM SHALL
 TERMINATE AT LEAST 4 FT BELOW, 4 FT
 HORIZONTALLY FROM OR 1 FT ABOVE OF THE
 ABOVE MENTIONED INTAKES. #6 THE BOTTOM
 OF THE VENT TERMINATION SHALL BE LOCATED
 AT 12 INCHES ABOVE FINISHED GRADE.
  
 2001 FBC(M)804.3.5 #3 WHERE VENT
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 STRUCTURE.
  