Plan Review Notes For Permit 05080065 |
Permit Number |
05080065 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-11-21 00:00:00 | PROVISO: | | SITE PLAN DOES NOT INDICATE DISTANCES | | FROM OPENING INTO THE HOME (DOORS, | | WINDOWS, OR FRESH AIR INTAKES).PER | | 2001 FBC(M)804.3.4 #3, VENT SYSTEM SHALL | | TERMINATE AT LEAST 4 FT BELOW, 4 FT | | HORIZONTALLY FROM OR 1 FT ABOVE OF THE | | ABOVE MENTIONED INTAKES. #6 THE BOTTOM | | OF THE VENT TERMINATION SHALL BE LOCATED | | AT 12 INCHES ABOVE FINISHED GRADE. | | | | 2001 FBC(M)804.3.5 #3 WHERE VENT | | TERMINATION IS LOCATED BELOW AN ADJACENT | | ROOF STRUCTURE, THE TERMINATION POINT | | SHALL BE LOCATED AT LEAST 3 FT FROM THE | | STRUCTURE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|