Plan Review Notes For Permit 05080065 |
Permit Number |
05080065 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-11-08 00:00:00 | | | PLEASE PROVIDE A SITE PLAN INDICATING | | THE LOCATION OF ALL SERVICE AND | | GENERATOR EQUIPMENT SO THAT COMPLIANCE | | WITH 225.31 THROUGH 225.37 CAN BE | | DETERMINED.ONLY THE GENERATOR WAS SHOWN | | ON THE RESUB. | | | | THE GEC CONNECTION NEEDS TO BE AT THE | | METER OR THE FIRST MEANS OF DISCONNECT, | | NOT THE TRANSFER SWITCH. PLEASE SHOW | | SAME. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|