 PLEASE PROVIDE A SITE PLAN INDICATING
 THE LOCATION OF ALL SERVICE AND
 GENERATOR EQUIPMENT SO THAT COMPLIANCE
 WITH 225.31 THROUGH 225.37 CAN BE
 DETERMINED.ONLY THE GENERATOR WAS SHOWN
 ON THE RESUB.
  
 THE GEC CONNECTION NEEDS TO BE AT THE
 METER OR THE FIRST MEANS OF DISCONNECT,
 NOT THE TRANSFER SWITCH. PLEASE SHOW
 SAME.
  