2005-08-24 00:00:00MECH.PLAN REVIEW:
  
 1. GENERATOR MANF. RECOMBINATION FOR
 AERVICE CLEARANCE/VENILATION IN
 FEET/INCHES IN ALL DIRECTION MUST ACCM.
 GENERATIR PERMIT APP. .
  
 2. GENERATOR EXHAUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENING, AND
 EXHAUST MUST BE DIRECTED AWAY FROM
 BUILDING .AND BE TEN FEET FROM PROPITY
 LINE.2001 FBC/M 804.3.3TERMINATION.
 2001 FBC/M SECTION 915
 REQUIRMENT OF NFPA 37
 8.2.3.2.
 3. INFORMATION ON TYPE OF FUEL.
  
 4.LP/NAT GAS REQUIRE PERMIT, FROM
 LICENSED GAS CONTRACTOR.
  
 PAT RAFTER 561/805/6719 OR 805/6719
 PATTY KRAUSS.
  
 PLEASE CALL IF THEAR ANY QUESTIONS.