Plan Review Notes For Permit 05080065 |
Permit Number |
05080065 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-08-24 00:00:00 | MECH.PLAN REVIEW: | | | | 1. GENERATOR MANF. RECOMBINATION FOR | | AERVICE CLEARANCE/VENILATION IN | | FEET/INCHES IN ALL DIRECTION MUST ACCM. | | GENERATIR PERMIT APP. . | | | | 2. GENERATOR EXHAUST MUST BE TEN FEET | | AWAY FROM ANY BUILDING OPENING, AND | | EXHAUST MUST BE DIRECTED AWAY FROM | | BUILDING .AND BE TEN FEET FROM PROPITY | | LINE.2001 FBC/M 804.3.3TERMINATION. | | 2001 FBC/M SECTION 915 | | REQUIRMENT OF NFPA 37 | | 8.2.3.2. | | 3. INFORMATION ON TYPE OF FUEL. | | | | 4.LP/NAT GAS REQUIRE PERMIT, FROM | | LICENSED GAS CONTRACTOR. | | | | PAT RAFTER 561/805/6719 OR 805/6719 | | PATTY KRAUSS. | | | | PLEASE CALL IF THEAR ANY QUESTIONS. |
|