Plan Review Notes
Plan Review Notes For Permit 05080048
Permit Number 05080048
Review Stop M
Sequence Number 1
Notes
Date Text
2005-08-19 00:00:00MECH. PLAN REVIEW:
  
 MECH. PROVISO:
  
 ELECTRICAL GENERATOR EXHAUST IS
 LOCATED MINIUM OF TEN FEET FROM THE
 PROPITY LOT LINE OR FROM ADJACENT
 BUILDING AND THE EXHAUST IS DIRECTED
 AWAY FROM THE BUILDING.
  
 THIS MEET INTENT OF THE MECH. CODE.
 2001 FBC/M 804.3.3 TERMINATION.
  
 2001 FBC/M SECTION 915
 REQUIRMENT OF NFPA 378.2.3.2
 EXHAUST SYSTEM TERMINATION.
  
 PAT RAFTER 561/805/6728 OR 805/6719
 PATTY KRAUSS.