Plan Review Notes For Permit 05080048 |
Permit Number |
05080048 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-08-11 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} IT APPEARS THE TRANSFER SWITCH | | REFEEDS THE METER. PLEASE CLARIFY | | | | 2} SUBMIT SPECS FOR THE GENERATOR AND | | TRANSFER SWITCH (TWO COPIES).SEE 225.31 | | THROUGH 225.37. | | | | 3} PLEASE SUBMIT A SITE PLAN INDICATING | | THE PHYSICAL LOCATION OF THE OF ALL | | SERVICE AND STANDBY EQUIPMENT SO | | COMPLIANCE WITH THE ABOVE MENTIONED | | ARTICLES CAN BE DETERMINED. | | | | 4} PLEASE SEE NOMINAL VOLTAGE FOR USE IN | | LOAD CALCS. 220.2, 240 VOLTS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|