Plan Review Notes
Plan Review Notes For Permit 05080028
Permit Number 05080028
Review Stop P
Sequence Number 1
Notes
Date Text
2005-08-12 00:00:00DENIED;
 1.PAGE E-1 HAS NOT BEEN SIGNED. (SEE
 ELECTRICAL NOTE 3)
 2.W/M AND L/T CANNOT CONNECT WITH A
 SANITARY CROSS. FBC-2001 PLUMBING SEC.
 706.3. INSTALL L/T ABOVE W/M OUTLET.
 3.A CLEANOUT IS REQUIRED ON W/M STACK AT
 48" ABOVE FINISH FLOOR, SHOW ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695