Plan Review Notes
Plan Review Notes For Permit 05071304
Permit Number 05071304
Review Stop E
Sequence Number 1
Notes
Date Text
2005-08-01 00:00:00******** UNSAT ********
  
 1)NOTE: PLEASE SEE THE MISSING REQUIRED
 "PRINTED NAME AND LICENSE NUMBER " FOR
 THE ARCHITECT OF RECORD ON PLANS.
 FAC 61G1-16.004
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH THE SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE "NOTES" TO POWER PLANS
 MENTIONS, "R" INDICATES RELOCATED
 OUTLETS TO EXSITING CIRCUITS? PLEASE SEE
 AN "R" COULD NOT BE LCOATED IF INDEED
 RECEPTS ARE EXSITNG.
  
 3)NOTE: PLEASE VERIFY BY NOTE IF TENANT
 OCCUPANTS HAVE ACCESS TO OVER CURRENT
 PROTECTIVE DEVICES FOR THEIR SPACE.
 IS BLDG UNDER 24 HR MANG?
 PLEASE SEE NEC 240.24
  
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELETCRICAL PLAN REVIEW
 561-805-6717
 [email protected]