2005-08-03 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05071304 |
| ADD: 580 VILLAGE BLVD |
| CONT: ANDERSON-MOORE |
| TEL: (561)662-1819 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)PROVIDE NOC RECORDED WITH THE CLERK |
| OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) 481.219 F.S.CERTIFICATE OF |
| AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| SHEET BEARING THE NAME OF AN ARCHITECT |
| PRACTICING UNDER A FICTITIOUS NAME, A |
| CORPORATION, OR A PARTNERSHIP, OFFERING |
| ARCHITECTURAL SERVICES, SHALL INCLUDE |
| THE CERTIFICATE OF AUTHORIZATION |
| NUMBER.ADD THE NUMBER TO EACH SHEET. |
| THIS MAY BE ADDED BY HAND. |
| |
| 3) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 4)TABLE 803.3 MINIMUM INTERIOR FINISH |
| CLASSIFICATION; PROVIDE INFORMATION |
| BASED ON INTERIOR FINISH REQUIREMENTS |
| BASED ON OCCUPANCY |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |
| |
| |
| |
| |