2005-08-19 00:00:00BUILDING REVIEW CHECKLIST:
 1- MINIMUM DESIGN PRESSURES SHALL BE
 10PSF AS REQUIRED BY SEC. 2002.4 FBC
 2001. SHEET #2 OF ENGINEERED DRAWINGS IS
 USING 6 PSF FOR ROOF BEAM. REVISE
 CALCULATIONS, WIND LOADS CHART AND
 GENERAL NOTE #10.
  
 2- APPLICATION CALLS FOR 18"X14" FOOTER,
 WHILE PLANS CALL FOR 12"X12".
 INFORMATION NEED TO MATCH AND SPECIFY
 FOOTING REINFORCEMENT. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 3- ENGINEERED DRAWINGS TO SPECIFY
 CONNECTION OF ALUMINUM POST TO THE
 FOOTER. SPECIFY SIZE, NUMBER AND HOW
 MUCH EMBEDMENT IS REQUIRED FOR THE
 ANCHORS. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
  
 4- ENGINEERED DRAWINGS TO SPECIFY SIZE
 OF STRUCTURAL GUTTER. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 5- SCREEN ENCLOSURE LAYOUT SHEET TO
 INCLUDE ENGINEER'S TITLE BLOCK AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 6- OWNER TO PROVIDE PROOF OF OWNERSHIP.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.