Date |
Text |
2005-08-01 00:00:00 | ******** UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE SEE PLANS MENTIONS A |
| NEW TRANSFORMER, HOWEVER THIS COULD NOT |
| BE LCOATED ON ELECTRICAL RISER DIAGRAM? |
| 215.5 |
| PLEASE REVISE DIAGRM TO INCLUDE ALL |
| WIRING. |
| |
| 2)NOTE: PLEASE SEE NEW"MPC", THIS DOES |
| NOT PROVIDE ENOUGH INFORMATION. DOES |
| THIS HAVE A MAIN? ETC ETC. |
| 215.5,240.4,310.16 |
| |
| 3)NOTE: PLEASE SEE "EQUIPMENT GROUNDING" |
| CONDUCTORS ARE BEING SHOWN FROM METER TO |
| "MAINS"/ FIRST MEANS OF DICSONNECT. |
| PLEASE SEE 250.6,250.24, "EQUIPMENT |
| GROUNDING" CONDUCTORS ARE ONLY INSTALLED |
| AFTER THE FIRST MEANS OF DISC. |
| |
| 4)NOTE: PLEASE SEE FS 471.003, WHICH |
| REQUIRED ALL PLANS FOR NEW 277/480V |
| SYSTEMS, TRANSFORMER ETC, TO BE SIGNED |
| DATED AND SEALED BY A FLORIDA REGISTERED |
| PE. PLEASE BE SURE PLANS HAVE ALL |
| CORRECT TITLE BLOCK INFORMATION AS |
| REQUIRED UNDER FAC 61G15-23.002 FOR |
| ENGINEER/ENGINEERING FIRM OF RECORD. |
| |
| 5)NOTE: PLEASE INCDICATE A PANEL |
| SCHEDULE WITH SIZE OF OCP, AWG FOR EACH |
| BRACH CIRCUIT. |
| PLEASE SHOW CONDUIT, CONDUCTORS SIZES, |
| CIRCUITS ON PLANS. |
| 215.5,240.4,310.16 ETC |
| |
| 6)NOTE: PLEASE SEE 240.21,408.16 WHICH |
| REQUIRES A MCB ON THE LOAD SIDE OF THE |
| TRANSFORMER. |
| |
| 7)NOTE: PLEASE SEE A MIN OF TWO GRNDS |
| RODS ARE REQUIRED. 250.50 |
| |
| 8)NOTE: PLEASE SEE BLDG REVIEW NOTES, |
| "ALL ELECTRICALSERVICE EQUIPMENT SHALL |
| BE INSTALLED A MIN OF 6" ABOVE BASED |
| FLOOD ELEVATION. THIS SHOULD BE NOTED ON |
| PLANS. |
| |
| PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICLA |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |