Plan Review Notes
Plan Review Notes For Permit 05071227
Permit Number 05071227
Review Stop B
Sequence Number 2
Notes
Date Text
2005-09-29 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05071227
 ADD: 1515 S FLAGLER DR
 CONT: CAROSEL DEV
 TEL: (561)966-0056
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
  
  
 1A) COMMENT FROM THE PREVIOUS REVIEW
 NUMBER 2A) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
  
  
 1B) COMMENT FROM THE PREVIOUS REVIEW,
 2B)FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)1) SLIDING DOORS - REPORT SUBMITTED
 AL-FAROOQ CORP. ARE MISSINGTHE
  
 FL COVERSHEET
 A)2) SUBMITTED AL-FAROOQ REPORTS ARE
 FOR NON-IMPACT AND SMALL MISSLE
 TESTING ONLY.
 A)3) THE MIAMI-DADE REPORTS SUBMITTED;
 04-1014.01 THIS REPORT WAS
 SUBMITTED WITHOUT THE TECHNICAL
 DRAWINGS, NO PRESSURES GIVEN!!!
 A)4) THE MIAMI-DADE REPORT SUBMITTED;
 04-0819.02(LARGE MISSLE) THE TYPE
 OF GLAZING TO BE USED NOT
 HIGHLIGHTED, NOR IS THE SILL
 HEIGHT INDICATED WHICH LIMITS THE
  
 PRESSURE.
 A)5) IF EITHER OF THE MIAMI-DADE
 REPORTS ARE TO BE USED, THEY ARE
 NOT LISTED ON THE FL STATE WEB
 SITE REQUIRING LOCAL PRODUCT
 APPROVAL. APPLICATION ATTACHED.
  
  
 B)1) HORIZONTAL SLIDING WINDOWS NO
 REPORT WAS SUBMITTED, THE
 CONTRACTOR INDICATED THAT THIS WAS
  
 TO BE A CUT DOWN VERSION OF THE
 SLIDING GLASS DOOR.
 B)2) THE SAME ISSUES AS LISTED ABOVE
 GLAZING TO BE HIGHLIGHTED TO WHICH
 TYPE OF GLAZING WILL BE USED.
 B)C) INDICATE THE TYPE OF BOTTOM TRACK
 (HEIGHT) TO BE USED, LIMITS
 PRESSURE.
  
  
 C)1) EFIS SYSTEMS- STO SUBMITTED FL
 COVERSHEET, MISSING THE BACK UP
 MIAMI-DADE REPORT.
 C)2) NOTE SINCE CONTRACTOR FAILED TO
 SUBMIT ONE OF THE REPORTS LISTED
 UNDER THE FL COVERSHEET THE
 BROCHURE SUBMITTED DOES STATE THAT
 THIS PRODUCT WAS TESTED WITH BOTH
 GYPSUM SHEATHING & PLYWOOD
 SHEATHING. THIS IS A MINIMUM TYPE
 I BUILDING, NO COMBUSTIBLE
 MATERIAL IN EXTERIOR WALL,SEE
 TABLE 600.
 D)1) CONTRACTOR SUBMITTED MANUFACTURES
 CUT SHEETS ON DENSGLASS GOLD
 EXTERIOR SHEATHING PANELS, BUT NO
  
 SUBMITTALS FILED UNDER THE FL.
 PRODUCT APPROVAL SYSTEM
 (COVERSHEET) NOR ES LEGACY REPORT
 D)2) RICHARDSON ENGINEERING SHEET LGN
 INDICATES THE GOVERNING DESIGN
 FOR WIND PRESSURE FOR LIGHT GAGE
 SYSTEM COMPONENTS AND CLADDING
 = -123PSF. PROVIDE REPORTS WITH
 SUCH VALUES.
 D)3) SHEET LGN STATES NOTE L-2 THAT
 SIGNED & SEALED CALCULATIONS MUST
 BE SUBMITTED FOR ALL EXTERIOR
 LIGHT GAGE FRAMING VERIFYING
 MEMBER SIZE & GAGE, LIGHT GAGE
 CONNECTIONS & CONNECTIONS OF
 LIGHT GAGE TO THE BUILDING
 STRUCTURE.NO CALCULATIONS
 SUBMITTED.
 D)4) NOTE, MOST EFIS REPORTS INDICATE
 THAT THIS SYSTEM IS NOT TO BE
 USED ON HORIZONTAL SURFACES.
  
 3)COMMENT #3 FROM THE PREVIOUS REIEW;
 FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED, PLANS
 DO NOT INDICATE IF NEGATIVE PRESSURES
 TAKEN ARE END ZONE PRESSUES AND WHAT
 TRIUTARY AREA (WINDOWS AND DOORS) WORST
 CASE 20 SQ FT.
 3)A) A WIND DESIGN SHEET FROM FRANK L.
  
 BENNARDO WAS SUBMITTED WITH
 POSITIVE AND NEGATIVE PRESSURES. A
  
 COPY OF THIS FORM IS TO BE
 RETAINED AND POSSIBLY BE
 FORWAARDED TO THE STATE FOR PEER
 REVIEW BY THE ENGINEERING BOARD.
 3)B)PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE
 DESIGN PROFESSIONAL AND BEING FILED
  
 FOR PUBLIC RECORD SHALL HAVE THE
 SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 3)C) THIS FORM STATES IT IS TO BE USED
 FOR DETERMINING PRELIMINARY DESIGN
 AND IS INTENDED FOR ESTIMATING
 PURPOSES ONLY!THE FORMAT USED IN
 THIS SIMPLIFIED VERSION CAN ONLY BE
  
 USED IN A BOX TYPE DESIGN.THIS IS
 METHOD 1 UNDER SECTION 6.4 ASCE
 7-98.
 3)D) METHOD 2 CAN NOT BE APPLIED SINCE
 6.5.1(1) REQUIRES THE BUILDING TO
 BE OF A REGULAR SHAPE, DEFINITION :
 A BUILDING OR OTHER STRUCTUE HAVING
 NO UNUSUAL GEOMETRICAL IRREGULARITY
  
 IN SPATIAL FORM.
 6.5.1(2) THE BUILDING OR STRUCTURE
 DOES NOT HAVE RESPONSE
 CHARACTERISTICS MAKING IT SUBJECT TO
  
 ACROSS-WIND LOAADING, VORTEX
 SHEDDING, INSTABILITY DUE TO
 GALLOPING OR FLUTTERING OR DOES NOT
 HAVE A SITE LOCATION FOR WHICH
 CHANNELING EFFECTS OR BUFFETING IN
 THE WAKE OF UPWIND OBSTRUCTIONS
 WARRENT SPECIAL CONSIDERATION.
 3)E) METHOD 3 IS A WIND TUNNEL TEST!!
  
 3)F) ASCE 7-98 6.5.6.5.2 BUILDINGS WITH
  
 A MEAN ROOF HEIGHT GREATER THAN 60'
 SHALL BE DESIGNED USING THE EXPOSURE
  
 RESULTING IN THE HIGHEST WIND LOADS
 FOR ANY WIND DIRECTION AT THE SITE.
 3)G) 1606.2.3 EDGE STRIPS AND END ZONES
 PROVIDE ELEVATIONS INDICATING WHICH
 AREAS ARE TO BE CONSIDERED AS END
 ZONES AND INTERIOR ZONES. TAKE WORST
  
 CASE 20 SQ. FT.
  
 4) FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 5) COMMENT # 5 FROM THE PREVIOUS REVIEW:
 STO DETAIL SHEETS INDICATE A SUPPORTING
 SUBSTRATE OR SUBSHEATHING, THE PLANS DO
 NOT IDENTIFY THIS MATERIAL, PLEASE
 IDENTIFY. SEE TYPE I SECTION 603 OR TYPE
 II SECTION 604 & TABLE 600.
 CONTRACTOR SUBMITTED A STO BROCHURE BUT
 PLANS NEED TO IDENTIFY WHAT THIS
 MATERIAL SHALL BE.
  
 6) ONCE THE STO PRODUCT APPROVALS ARE
 SUBMITTED THE REQUIREMENTS FOR 2603.6
 WILL BE REVIEWED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
 NOTE : WORKING ON THE EXTERIOR OF THIS
 BUILDING WILL RESULT IN PAYING 4X THE
 FEE FOR WORKING WITHOUT A PERMIT!!!!!!!
  
  
 NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
  
  
  
  
  
  
  
  
  
  
  